Load Flow Analysis
You will try it with the PowerWorld simulator!
Electric Power Systems L5 - Olof Samuelsson
1
Outline • • • • • •
Real and reactive power Line transfer The load flow problem Gauss-Seidel Newton-Raphson (Fast) Decoupled Power Flow Electric Power Systems L5 - Olof Samuelsson
2
Real and reactive power P & Q Z
X
j
xI
V
xI
j
S
Q
j
R
P
Z=R+jX V=(R+jX)I R=Zcosj X=Zsinj cosj=power factor j>0 ind/lagging j<0 cap/leading
S=P+jQ P=Scosj; heat, work Q=Ssinj; E&M fields
Electric Power Systems L5 - Olof Samuelsson
3
Power through inductance Xline
• Line transfer
Xeq
• Power through transformer Xd
• Power from generator
Electric Power Systems L5 - Olof Samuelsson
4
Line transfer 1 I1 Z=Z a I2 V1=V1 q1
S12
S21
V2=V2 q2
S12=P12+jQ12=V1I1*=V1((V1-V2)/Z)* P12=V12 /Zcosa-V1V2/Zcos(q1-q2+a) Q12=V12 /Zsina-V1V2/Zsin(q1-q2+a)
Electric Power Systems L5 - Olof Samuelsson
5
Line transfer 2 Z≈jX, a≈90°: P12=V1V2/Xsin(q1-q2) Q12=V12 /X-V1V2/Xcos(q1-q2)
P12 Pmax
V1,V2 constant
P21=V1V2/Xsin(q2-q1) Q21=V22 /X-V1V2/Xcos(q2-q1) P12=-P21 Q12≠-Q21 if V1≠V2
q1-q2 Pmax=V1V2/X
Electric Power Systems L5 - Olof Samuelsson
6
The load flow problem In a network with known parameters, find V,q at all buses given generation and load •Balance equations at each bus: Pin(gen – load) – Pout(to other buses)=0 Qin(gen – load) – Qout(to other buses)=0 •Equations nonlinear and coupled •Postprocessing => line flows and losses Electric Power Systems L5 - Olof Samuelsson
7
DALAM ANALISIS ALIRAN DAYA DIHITUNG : 1. TEGANGAN TIAP-TIAP BUS 2. ALIRAN DAYA PADA TIAP-TIAP SALURAN ALIRAN DAYA PADA SALURAN i-j DITENTUKAN SEBAGAI BERIKUT :
S ij Vi I ij* Vi V j Vi zij
*
Zij = Impedansi Saluran i-j
Electric Power Systems L5 - Olof Samuelsson
8
Power balance at each bus PGk+jQGk Vk qk Load
…
PLk+jQLk
To rest of system
•Balance equations at bus k: Pin– Pout=0 Qin– Qout=0 •Pin and Qin Generation minus load •Pout and Qout line transfer to buses i≠k Depend on Vi and qi Electric Power Systems L5 - Olof Samuelsson
9
Three bus types • Swing or slack bus – Reference with V and q known
• PV or generator bus – Voltage controlled, V known
• PQ or load bus – Neither V nor q known
Electric Power Systems L5 - Olof Samuelsson
10
LOAD BUS (PQ BUS) : - Terhubung dengan beban - P,Q dari beban diketahui dan tetap - |V| dan q (sudut fasa) tegangan dihitung GENERATOR BUS (PV BUS) : - Terhubung dengan generator - P, |V| dari generator diketahui dan tetap - q dan Q (daya reaktif generator) dihitung
SWING/SLACK BUS : - Terhubung dengan generator - |V| dan q = 0° (referensi) dari generator diketahui dan tetap - P dan Q dihitung - Mencatu rugi2 daya dan beban yang tidak dapat di supply oleh generator lain Electric Power Systems L5 - Olof Samuelsson
11
ANALISIS ALIRAN DAYA (Load Flow Analysis)
METODE GAUSS-SEIDEL
Electric Power Systems L5 - Olof Samuelsson
12
DATA SALURAN Saluran
R (pu)
X(pu)
1-2
0,10
0,40
1-4
0,15
0,60
1-5
0,05
0,20
2-3
0,05
0,20
2-4
0,10
0,40
3-5
0,05
0,20
DATA BUS
Dimisalkan/ Harga awal
Tetap
Bus
P (pu)
Q(pu)
V (pu)
Keterangan
1
…….
……..
1,02 0°
Swing/Slack Bus
2
- 0,6
- 0,3
1,00 0°
Load Bus
3
1,0
…….
1,04 0°
Generator Bus
4
- 0,4
- 0,1
1,00 0°
Load Bus
5
- 0,6
- 0,2 Electric 1,00 Bus 0°SystemsLoad Power L5 - Olof Samuelsson
13
ADMITANSI SALURAN Saluran
G (pu)
B(pu)
1-2
0,588235
- 2,352941
1-4
0,392157
- 1,568627
1-5
1,176471
- 4,705882
2-3
1,176471
- 4,705882
2-4
0,588235
- 2,352941
3-5
1,176471
- 4,705882
YBUS =
Y11 Y21 0,0 Y41 Y 51
Y12 0,0 Y14 Y15 Y22 Y23 Y24 0,0 Y32 Y33 0,0 Y35 Y42 0,0 Y44 0,0 0,0 Y53 0,0 Y55
Electric Power Systems L5 - Olof Samuelsson
14
LOAD BUS (Bus 2) n
Pi - jQi Vi*
V Y
j ij
j 1
5
P2 - jQ2 V2*
V Y
j 2j
j 1
V2* Y21V1 Y22V2 Y23V3 Y24V4
1 V2 Y22
P2 - jQ2 Y21V1 Y23V3 Y24V4 * V2 Electric Power Systems L5 - Olof Samuelsson
15
Elemen Matrix Ybus : Y21 = -0,588235 + j2,352941 pu Y22 = 2,352941 - j9,411764 pu Y23 = -1,176471 + j4,705882 pu Y24 = -0,588235 + j2,352941 pu Y25 = 0,0 +j0,0
Tegangan bus 2 pada iterasi 1 V2(1)
1 0,6 j 0,3 (0,588235 j 2,352941)(1,02) Y22 1,0 j 0,0 (1,176471 j 4,705882)(1,04) (0,588235 j 2,352941)(1,0)
1 1,811764 j9,347058 (0,6 j 0,3 2,411764 j 9,647058) Y22 2,352941 j 9,411764 0,980000 jElectric 0,052500 puSystems L5 - Olof Power Samuelsson
16
Koreksi (OPTIONAL) : (1) 2
V
1 0,6 j 0,3 2,411764 j 9,647058 Y22 0,980000 j 0,052500 0,976351 j 0,050965 pu
Electric Power Systems L5 - Olof Samuelsson
17
GENERATOR BUS (Bus 3) 5
P3 - jQ3 V3*
V Y
j 3j
j 1
V3* Y32V2 Y33V3 Y35V5
Q3 Im V3* Y32V2 Y33V3 Y35V5
1 P3 - jQ3 V3 Y32V2 Y35V5 * Y33 V3 Electric Power Systems L5 - Olof Samuelsson
18
Elemen Matrix Ybus : Y31 = 0,0 + j0,0 pu Y32 = - 1,176471 + j4.705882 pu Y33 = 2,352941 - j9,411764 pu Y34 = - 0,0 + j0,0 pu Y35 = -1,176471 + j4,705882 pu
Tegangan bus 3 pada iterasi 1 Q3(1) Im1.04(1,176471 j 4,705882)(0,976351 j 0,050965) (2,352941 j 9,411764)(1,04) (1,176471 j 4,705882)(1,0) pu 0,444913 pu Electric Power Systems L5 - Olof Samuelsson
19
V3(1)
1 1,0 j 0,444913 (1,176471 j 4,705882)( 0,976351 j 0,050965) Y33 1,04 j 0,0 (1,176471 j 4,705882)(1,0)
1 (0,961538 j 0,4277801 2,085285 j 9,360334) Y33
3,046823 j 9,788135 1,054984 j 0,059979 pu 2,352941 j 9,411764
Koreksi : V3(1) 1,056688 V3(1)
1,04 1,054984 j 0,059979 1,038322 j 0,059032 pu 1,056688 Electric Power Systems L5 - Olof Samuelsson
20
Iter 0
Iter 1
∆V
Koreksi (α=1,6)
Iter 2
V1(0) : 1,02+j0,0
V1(1) : 1,02+j0,0
∆V1 : V1(1) – V1(0)
V1(1) : 1,02+j0,0
V1(2) : 1,02+j0,0
V2(0) : 1,00+j0,0
V2(1) : 0,97635 -
∆V2 : V2(1) – V2(0)
V2(1) : V2(0)+α∆V2
V2(2) : ---
∆V3 : V3(1) – V3(0)
V3(1) : optional
V3(2) : ---
j0,050965
V3(0) : 1,04+j0,0
V3(1) : 1,03832 + j0,059032
V4(0) : 1,00+j0,0
V4(1) : ---- +j ----
∆V4 : V4(1) – V4(0)
V4(1) : V4(0)+α∆V4
V4(2) : ---
V5(0) : 1,00+j0,0
V5(1) : ---- +j ----
∆V5 : V5(1) – V5(0)
V5(1) : V5(0)+α∆V5
V5(2) : ---
?
SEMUA ∆V < TOLERANSI (0,0001) YA STOP ITERASI TIDAK Power ITERASI DILANJUTKAN Electric Systems L5 - Olof Samuelsson
21
∆V
Iter 0
Iter 1
V1(0) : 1,02+j0,0
V1(1) : 1,02+j0,0
∆V1 : V1(1) – V1(0)
V1(1) : 1,02+j0,0
V1(2) : 1,02+j0,0
V2(0) : 1,00+j0,0
V2(1) : 0,97635 -
∆V2 : V2(1) – V2(0)
V2(1) : V2(0)+α∆V2
V2(2) : ---
∆V3 : V3(1) – V3(0)
V3(1) : optional
V3(2) : ---
∆V4 : V4(1) – V4(0)
V4(1) : V4(0)+α∆V4
V4(2) : ---
∆V5 : V5(1) – V5(0)
V5(1) : V5(0)+α∆V5
V5(2) : ---
j0,050965
V3(0) : 1,04+j0,0
V3(1) : 1,03832 + j0,059032
V4(0) : 1,00+j0,0
V4(1) : 0,86218 j 0,325
V5(0) : 1,00+j0,0
V5(1) : 0,99413 -j 0,025097
Koreksi (α=1,6)
Iter 2
?
SEMUA ∆V < TOLERANSI (0,0001) YA STOP ITERASI TIDAK Power ITERASI DILANJUTKAN Electric Systems L5 - Olof Samuelsson
22
TUGAS 5 • Cari sistem 7 – 10 bus, run prog. LoadFlow GS (Q gen tdk ada batas) • Check apakah proses iterasi sdh konvergen • Cari teori (H. Saadat) meng. Qmin & Qmax • Run lagi sistem diatas dng batas Qmin & Qmax (MATLAB : Qgen ≠ Qmax, why??? check dng software yg lain) • Gunakan Qc dan Ql utk pegaturan teg.bus • Buat analisis hasil simulasi
Electric Power Systems L5 - Olof Samuelsson
23
ANALISIS ALIRAN DAYA (Load Flow Analysis)
METODE NEWTON-RAPHSON
Electric Power Systems L5 - Olof Samuelsson
24
Fungsi Nonlinear dengan 1 (satu) Variabel
Menentukan harga x, untuk F(x)=0 dengan Metode Newton-Raphson Electric Power Systems L5 - Olof Samuelsson
25
Fungsi dengan 1 (satu) variabel
f ( x) 0 Dengan menggunakan Deret “TAYLOR” :
1 df ( x0 ) 1 d 2 f ( x0 ) f ( x) f ( x0 ) ( x x0 ) ...... 2 1! dx 2! dx 1 d n f ( x0 ) ...... n! dx n Dengan pendekatan LINEAR :
df ( x0 ) f ( x ) f ( x0 ) ( x x0 ) 0 dx Electric Power Systems L5 - Olof Samuelsson
26
df ( x0 ) ( x x 0 ) f ( x ) f ( x0 ) dx Secara umum dapat dinyatakan :
df ( x) x f dx Electric Power Systems L5 - Olof Samuelsson
27
Fungsi dengan 2 (dua) variabel
f1 ( x1 , x2 ) 0 f 2 ( x1 , x2 ) 0 Persamaan yg digunakan pada setiap iterasi :
f1 x 1 f 2 x 1
f1 x f 1 1 x2 f 2 x2 f 2 x2 Electric Power Systems L5 - Olof Samuelsson
28
Contoh : Generator
y23 4 j10
P2 1,70 V2 1,1249
2
3
y13 4 j5
Load P3 2,0 Q3 1,0
Slack
1 V1 1,000
4 j5 0 j 0 4 j5 Ybus 0 j 0 4 j10 4 j10 4 j 5 4 j10 8 j15 Electric Power Systems L5 - Olof Samuelsson
29
Persamaan Nonlinear : P1 V1 V1 G11 V1 V3 G13Cos(q1 q 3 ) V1 V3 B13Sin(q1 q 3 ) Q1 V1 V3 G13Sin(q1 q 3 ) V1 V1 B11 V1 V3 B13Cos(q1 q 3 ) P2 V2 V2 G22 V2 V3 G23Cos(q 2 q 3 ) V2 V3 B23Sin(q 2 q 3 )
Q2 V2 V3 G23Sin(q 2 q3 ) V2 V2 B22 V2 V3 B23Cos(q 2 q3 ) P3 V3 V1 G31Cos(q 3 q1 ) V3 V2 G32Cos(q 3 q 2 ) V3 V3 G33 V3 V1 B31 Sin(q 3 q1 ) V3 V2 B32Sin(q 3 q1 )
Q3 V3 V1 G31Sin (q 3 q1 ) V3 V2 G32Sin (q 3 q 2 ) V3 V1 B31 Cos (q 3 q1 ) V3 V2 B32 cos(q 3 q 2 ) V3 V3 B33 Electric Power Systems L5 - Olof Samuelsson
30
PERSAMAAN-PERSAMAAN DIATAS MERUPAKAN FUNGSI DARI V DAN TIAP-TIAP BUS
q PADA
PERSAMAAN-PERSAMAAN DIATAS DIGUNAKAN UNTUK MENGHITUNG V DAN q DARI TIAP-TIAP BUS.
Electric Power Systems L5 - Olof Samuelsson
31
Persamaan yang digunakan pada setiap iterasi : P1 q 1 Q1 q 1 P2 q1 Q 2 q1 P 3 q1 Q3 q 1
P1 V1 Q1 V1 P2 V1 Q 2 V1 P3 V1 Q3 V1
P1 q2 Q1 q2 P2 q2 Q 2 q2 P3 q2 Q3 q2
P1 V2 Q1 V2 P2 V2 Q 2 V2 P3 V2 Q3 V2
P1 q3 Q1 q3 P2 q3 Q 2 q3 P3 q3 Q3 q3
P1 V3 Q1 V3 P2 V3 Q 2 V3 P3 V3 Q3 V3
Electric Power Systems L5 - Olof Samuelsson
q1 P1 V Q 1 1 q2 P2 V2 Q 2 q P 3 3 V3 Q3
32
P1 q 1 Q1 q 1 P2 q1 Q 2 q1 P 3 q1 Q3 q 1
P1 V1 Q1 V1 P2 V1 Q 2 V1 P3 V1 Q3 V1
P1 q2 Q1 q2 P2 q2 Q 2 q2 P3 q2 Q3 q2
Bus 1 : Slack
P1 V2 Q1 V2 P2 V2 Q 2 V2 P3 V2 Q3 V2
P1 q3 Q1 q3 P2 q3 Q 2 q3 P3 q3 Q3 q3
P1 V3 Q1 V3 P2 V3 Q 2 V3 P3 V3 Q3 V3
q1 P1 V Q 1 1 q2 P2 V2 Q 2 q P 3 3 V3 Q3
Bus 2 : Gen. bus
Electric Power Systems L5 - Olof Samuelsson
33
P2 q2 P3 q 2 Q3 q 2
P2 q3 P3 q3 Q3 q3
JACOBIAN Matrix
P2 V3 P3 V3 Q3 V3
P2 q 2 P3 q 2 Q3 q 2
q2 P2 q P 3 3 V3 q3
P2 q 3 P3 q 3 Q3 q 3
P2 V3 V3 P3 V3 V3 Q3 V3 V3
q 2 q 3 V3 V3
Electric Power Systems L5 - Olof Samuelsson
P 2 P3 Q 3
34
H ij
Pi q j
Qi J ij q j
H 22 H 23 N 23 q 2 H q H N 33 33 3 32 J 32 J 33 L33 V3 V3 JACOBIAN
N ij
Lij
Pi Vj Qi
Vj
P 2 P3 Q3
Electric Power Systems L5 - Olof Samuelsson
Vj
Vj
q 2( k 1) q 2( k ) q 2 q 3( k 1) q 3( k ) q 3 V3
( k 1)
V3
35
(k )
V3
SECARA UMUM DAPAT DITULIS :
q H N J L V V JACOBIAN
P Q
Electric Power Systems L5 - Olof Samuelsson
36
Iterasi 1 : P2 P2 {V2 V2 G22 V2 V3 G23Cos (q 2 q 3 ) V2 V3 B23Sin (q 2 q 3 )} P 2 1.70 {(1.1249)(1.1249)(4) (1.1249)(1.0)(4)Cos (0 0) (1.1249)(10) Sin (0 0) P2 1.70 {5.0615 (4.4996)} 1.70 0.562 1.138
P3 P3 {V3 V1 G31Cos (q 3 q1 ) V3 V2 G32Cos (q 3 q 2 ) V3 V3 G33 V3 V1 B31 Sin (q 3 q1 ) V3 V2 B32Sin (q 3 q 2 )} P3 2 {(1.0)(1.0)(4)Cos (0 0) (1.0)(1.1249)(4)Cos (0 0) (1.0)(1.0)(8) (1.0)(1.)(5) Sin (0 0) (1.0)(1.11249)(10) Sin (0 0)} P3 2 0.4996 1.5004.
Q3 Q3 {V3 V1 G31Sin (q 3 q1 ) V3 V2 G32Sin (q 3 q 2 ) V3 V1 B31 Cos (q 3 q1 ) V3 V2 B32Cos (q 3 q 2 ) V3 V3 B33} Q3 1 {0 0 5 11.249 15} 0.24 Electric Power Systems L5 - Olof Samuelsson
37
H 22
P2 {V2 V2 G22 V2 V3 G23Cos (q 2 q 3 ) V2 V3 B23 Sin (q 2 q 3 )} q 2 q 2
H 22 0 (1.1249)(1.0)(4) Sin (0 0) (1.1249)(1.0)(10)Cos (0 0) H 22 0 0 11.249 11.249
H 23
P2 {V2 V2 G22 V2 V3 G23Cos (q 2 q 3 ) V2 V3 B23Sin (q 2 q 3 )} q 3 q 3
H 23 0 (1.1249)(1.0)(4){ Sin (0 0)}(1) (1.1249)(1.0)(10){Cos (0 0)}(1) H 23 11.249
N 23 V3
P2 0 (1.1249)(4)Cos (0 0) (1.1249)(10) Sin (0 0) V3
N 23 0 4.4996 0 4.4996 Electric Power Systems L5 - Olof Samuelsson
38
H 32
P3 {V3 V1 G31Cos (q 3 q 1 ) V3 V2 G32Cos (q 3 q 2 ) V3 V3 G33 q 2 q 2
V3 V1 B31Sin (q 3 q 1 ) V3 V2 B32 Sin (q 3 q 2 )} 0 (1.0)(1.1249)(4){ Sin (0 0) 0 (1.0)(1.0)(5){Cos (0 0)} (1.0)(1.1249)(10)(1) 11.249
H 33
P3 {V3 V1 G31Cos (q 3 q 1 ) V3 V2 G32Cos (q 3 q 2 ) V3 V3 G33 q 3 q 3
V3 V1 B31Sin (q 3 q 1 ) V3 V2 B32 Sin (q 3 2 )} 0 0 0(1.0)(1.0)(5){Cos (0 0)}(1) (1.0)(1.1249)(10){Cos (0 0)}(1) 16.249
N 33 V3
P3 V3 {V3 V1 G31Cos (q 3 q1 ) V3 V2 G32Cos (q 3 q 2 ) V3 V3 G33 V3 V3
V3 V1 B31Sin (q 3 q1 ) V3 V2 B32Sin (q 3 q 2 )} (1.0)(4)Cos (0 0) (1.1249)(4)Cos (0 0) (2)(1)(8) 0 0 7.5004 Electric Power Systems L5 - Olof Samuelsson
39
J 32
Q3 {V3 V1 G31Sin (q 3 q 1 ) V3 V2 G32 Sin (q 3 q 2 ) V3 V1 B31Cos (q 3 q 1 ) q 2 q 2
V3 V2 B32Cos (q 3 q 2 ) V3 V3 B33} 0 (1.0)(1.1249)(4){Cos (0 0)}(1) 0 (1)(1.1249)(10){ Sin (0 0)}(1) 4.4996
J 33
Q3 {V3 V1 G31Sin (q 3 q 1 ) V3 V2 G32 Sin (q 3 q 2 ) V3 V1 B31Cos (q 3 q 1 ) q 3 q 3
V3 V2 B32Cos (q 3 q 2 ) V3 V3 B33} (1.0)(1.0)(4){Cos (0 0)}(1) (1.0)(1.1249)(4){Cos (0 0)}(1) 0 0 0 8.4996
L33 V3
Q3 V3 {V3 V1 G31Sin (q 3 q1 ) V3 V2 G32Sin (q 3 q 2 ) V3 V1 B31Cos (q 3 q1 ) V3 V3
V3 V2 B32Cos (q 3 q 2 ) V3 V3 B33} 0 0 (1.0)(5){Cos (0 0)} (1.1249)(10){Cos (0 0)} (2)(1.0)(15) 13.751 Electric Power Systems L5 - Olof Samuelsson
40
q 2 q 3 V3 V3
q 2 q 3 V3 V3
11.249 11.249 4.4996 16.249 7.5004 = 11.249 4.4996 8.4996 13.7510
=
0.2844 0.1911 0.0112 0.1866 0.1733 0.0334 0.0223 0.0446 0.0557
Electric Power Systems L5 - Olof Samuelsson
-1
1.138 1.5004 0.249
1.138 1.5004 0.249
41
0.0341 q 2 0.0341 q 2 x180 1.955 3.14 0.056 q 3 0.056 q 3 x180 3.21 3.14 V3 0.0277 V3 0.0277 x1.0 0.0277 V3
q 2' q 20 q 2 0 1.955 1.955 q 3' q 30 q 3 0 (3.21) 3.21 V3' V30 V3 1 (0.0277) 0.9723 pu TUGAS 6 ………….. (2 iterasi) Electric Power Systems L5 - Olof Samuelsson
42
Generator
Slack 3
2
H 22 H 32 J 32
H 23 H 33 J 33
Load
N 23 N 33 L33
q 2 q 3 V3 V3
1
P2 = P3 Q3
JACOBIAN
Electric Power Systems L5 - Olof Samuelsson
43
Generator
Load
1
2
H 22 H 32 J 32
H 23 H 33 J 33
Slack
N 23 N 33 L33
q 2 q 3 V3 V3
3
P2 = P3 Q3
JACOBIAN
Electric Power Systems L5 - Olof Samuelsson
44
Generator
Load
1
2
Slack
3
P2 H 23 {V2 V1 G21Cos (q 2 q1 ) V2 V2 G22 V2 V1 B21Sin (q 2 q1 )} q 3 q 3 0
H 22 0 0
0 H 33 J 33
0 N 33 L33
JACOBIAN
q 2 q 3 V3 V3
Electric Power Systems L5 - Olof Samuelsson
P2 = P3 Q3 45
TUGAS 7 • Cari sistem 7 – 10 bus, run prog. LoadFlow NR (Q gen tdk batas) • Check apakah proses iterasi sdh konvergen • Run lagi sistem diatas dng batas Qmin & Qmax • Gunakan Qc dan Ql utk pegaturan teg.bus • Bandingkan dengan hasil dari metode GS • Print elemen Jacobian Matrix
Electric Power Systems L5 - Olof Samuelsson
46
TUGAS 7 • Cari sistem 7 – 10 bus, run prog. Load-Flow NR (Q gen tdk batas)(14 bus & 30 bus IEEE) • Check apakah proses iterasi sdh konvergen • Run lagi sistem diatas dng batas Qmin & Qmax • Gunakan Qc dan Ql utk pegaturan teg.bus • Bandingkan dengan hasil dari metode GS • Tuliskan persamaan yg digunakan pada setiap iterasi metode NR • Hitung 2(dua) elemen matrix Jacobian dan 1 (satu) ∆P atau ∆Q
Electric Power Systems L5 - Olof Samuelsson
47
ANALISIS ALIRAN DAYA (Load Flow Analysis)
METODE FAST-DECOUPLED
Electric Power Systems L5 - Olof Samuelsson
48
Jaringan transmisi umumnya memiliki perbandingn X/R yang tinggi. Perubahan daya aktif sistem [P] hampir tidak berpengaruh terhadap perubahan magnitude tegangan [V], namun sangat berpengaruh terhadap perubahan sudut phase []. Perubahan daya reaktif sistem [Q] sangat berpengaruh terhadap perubahan magnitude tegangan [V], namun hampir tidak berpengaruh terhadap perubahan sudut phase [].
Electric Power Systems L5 - Olof Samuelsson
49
Sehingga elemen matrix Jacobian N dan J bisa diabaikan (bernilai nol) :
P H Q 0
0 V L V
Diperoleh persamaan berikut (decoupled) :
P H V Q L V Electric Power Systems L5 - Olof Samuelsson
50
Dimana elemen matrix Jacobian H dan L dapat dinyatakan sbb. :
H ij ViV j (Gij sin ij Bij cos ij )
i j
H ii BiiVi 2 Qi
i j
Lij ViV j (Gij sin ij Bij cos ij ) H ij
i j
Lii BiiVi 2 Qi
i j
Electric Power Systems L5 - Olof Samuelsson
51
Asumsi dasar yang digunakan: 1. Sistem memiliki rasio X/R yang tinggi. Dengan demikian:
Gij sin ij Bij 2. Perbedaan antara sudut tegangan bus sangat kecil, sehingga:
sin ij sin( i j ) 0 cos ij cos( i j ) 1.0 3. Juga:
Qi BiiVi 2 Electric Power Systems L5 - Olof Samuelsson
52
Maka, persamaan „decoupled‟ diatas dapat dituliskan sbb. :
P V t B'V V Q V B"V V
t
B‟ dan B‟‟ adalah negatif dari bagian imajiner elemen matrix Ybus. Matrix B‟ mempunyai orde (n-1) dan matrix B‟‟ mempunyai orde (n-1-m), dimana m adalah jumlah dari Generator (PV) Bus. Electric Power Systems L5 - Olof Samuelsson
53
Selanjutnya, dilakukan modifikasi tambahan dengan asumsi-asumsi sbb. : elemen yang sangat berpengaruh terhadap aliran daya reaktif, seperti reaktansi shunt dan off-nominal tap trafo dihilangkan dari B‟. pengaruh pergeseran sudut dari phase shifter dihilangkan dari B”. membagi setiap persamaan diatas dengan Vt, kemudian V di set 1.0
Electric Power Systems L5 - Olof Samuelsson
54
Persamaan yang digunakan pada setiap iterasi dengan metode Fast Decoupled adalah sbb. :
P B' V Q B"V V Electric Power Systems L5 - Olof Samuelsson
55
Contoh Sistem Tenaga Listrik dng 5 Bus :
~ 2
1
~
~
5
3
4
Electric Power Systems L5 - Olof Samuelsson
56
Data Saluran : Bus
Impedansi
Line Charging
Admitansi
P–Q
Zpq
Ycpq/2
Ypq
1-2
0.080+j0.240
0.0+j0.0102
1.250-j3.750
1-3
0.020+j0.060
0.0+j0.0077
5.000-j15.00
1-4
0.080+j0.240
0.0+j0.0102
1.250-j3.750
2-3
0.060+j0.180
0.0+j0.0077
1.666-j5.000
2-5
0.000+j0.060
0.0+j0.0077
5.000-j15.000
3-4
0.080+j0.240
0.0+j0.0102
1.250-j3.750
3-5
0.060+j0.180
0.0+j0.0077
1.666-j5.000
Electric Power Systems L5 - Olof Samuelsson
57
Data Bus : BUS
V-bus
P(pu)
Q(pu)
1 ( Slack )
1.00<0
-
-
2 ( Gen1 )
1.03<0
0.2
-
3 ( Load1 )
1.00<0
-0.06
-0.02
4 ( Load2 )
1.00<0
-0.05
-0.01
5 ( Gen2 )
1.03<0
0.5
-
Electric Power Systems L5 - Olof Samuelsson
58
Matrix Ybus :
7.50 j 22.5 1.25 j3.75 5.0 j15.0 1.25 j3.75 0
1.25 j3.75 5.0 j15.0 1.25 j3.75 0 7.92 j 23.75 1.67 j5.0 0 5.0 j15.0 1.67 j5.0 9.58 j 28.75 1.25 j3.75 1.67 j5.0 0 1.25 j3.75 2.5 j 7.5 0 5.0 j15.0 1.67 j5.0 0 6.67 j 20.0
Electric Power Systems L5 - Olof Samuelsson
59
Matrix B‟ :
7.50 j 22.5 1.25 j3.75 5.0 j15.0 1.25 j3.75 0
1.25 j3.75 5.0 j15.0 1.25 j3.75 0 7.92 j 23.75 1.67 j5.0 0 5.0 j15.0 1.67 j5.0 9.58 j 28.75 1.25 j3.75 1.67 j5.0 0 1.25 j3.75 2.5 j 7.5 0 5.0 j15.0 1.67 j5.0 0 6.67 j 20.0
Electric Power Systems L5 - Olof Samuelsson
60
Matrix B‟ :
23.75 5.0 0 15.0
5.0 28.75 3.75 5.0
0 15.0 3.75 5.0 7.5 0 0 20.0
Electric Power Systems L5 - Olof Samuelsson
61
Matrix B‟‟ : 7.50 j 22.5 1.25 j3.75 1.23 j3.75 7.92 j 23.75 5.0 j15.0 1.67 j5.0 0 1.25 j3.75 0 5.0 j15.0
5.0 j15.0 1.67 j 5.0
1.25 j3.75 0 0 5.0 j15.0 9.58 j 28.75 1.25 j3.75 1.67 j5.0 1.25 j3.75 2.5 j 7.5 0 1.67 j 5.0 0 6.67 j 20.0
Electric Power Systems L5 - Olof Samuelsson
62
Matrix B‟‟ :
28.75 3.75
3.75 7.5
Persamaan yang digunakan pada setiap iterasi dengan metode Fast Decoupled adalah sbb. : Electric Power Systems L5 - Olof 63 Samuelsson
P2 V 2 P3 V 3 P4 V4 P 5 V5
23.75 5.0 0 15.0
Q3 V 3 Q4 V 4
28.75 3.75
5.0 28.75 3.75 5.0
0 15.0 2 3.75 5.0 3 7.5 0 4 0 20.0 5
3.75 V3 7.5 V4
Electric Power Systems L5 - Olof Samuelsson
64
TUGAS 8 • Cari sistem 7 – 10 bus, run prog. LoadFlow FD (Q gen tdk batas) • Check apakah proses iterasi sdh konvergen • Run lagi sistem diatas dng batas Qmin & Qmax • Gunakan Qc dan Ql utk pegaturan teg.bus • Bandingkan dengan hasil dari metode GS dan NR.
Electric Power Systems L5 - Olof Samuelsson
65
TUGAS 8 • Cari sistem 7 – 10 bus, run prog. Load-Flow FD (Q gen tdk ada batas) (14 bus & 30 bus IEEE) • Check apakah proses iterasi sdh konvergen • Run lagi sistem diatas dng batas Qmin & Qmax • Gunakan Qc dan Ql utk pegaturan teg.bus • Bandingkan dengan hasil dari metode GS dan NR. • Pelajari pengaruh tap trafo dan phase shifter thd elemen matrix Ybus
Electric Power Systems L5 - Olof Samuelsson
66
• Print elemen matrix Jacobian dan B‟ & B” (check secara manual) • Run program Matlab dng memasukkan Qmin & Q max, Qc & Ql utk pengaturan tegangan • Check Q yg dibangkitkan generator (Q>Qlimit atau Q
Electric Power Systems L5 - Olof Samuelsson
67