Microface Hiromatic G Addendum
Nederlands
code 271641 --- rev. 19.01.2001
Issued by TDS
1. Alarm Lijst MICROFACE CODE A1 A2 A3 A4 A5 A6
MICROFACE BERICHT "HP1" "LP1" "HC" "LC" "EHO" "AF"
HIROMATIC BERICHT
Type
"COMPR. 1 HOGEDRUK STORING" "COMPR. 1 LAGEDRUK STORING" "TE VEEL GEKOELD WATER” "TE WEINIG WATER" "E-VERHITTERS OVERVERHIT" "VENTILATOR DEFECT"
A7
"AF"
"VENTILATOR DEFECT"
A8 A9 A10 A11 A12 A13 A14 A15 A16 A17 A18 A19 A20 A21 A22 A23 A24 A25 A26 A27
"CF" "LE" "LE" "UI1" "UI1" "HFA" "HHC" "HF" "HN" "HUC" "HrT" "LrT" "HrH" "LrH" "HTE" "LTE" "HHE" "LHE" "HE" "HC1"
A28
"HH"
A29 A30 A31 A32 A33
"PtC" "rSF" "rSF" "ESF" "SF"
A34 A35 A36 A37 A38 A39 A40 A41 A42 A43 A44 A45 A46 A47 A48 A49 A50 A51
"NET" "or" -
"VERVUILD FILTER" "WATER LEKKAGE" "WATER LEKKAGE" "GEBRUIKERS INGANG 1 INWERKING" "GEBRUIKERS INGANG 1 INWERKING" "BEVOCHTIGER DEFECT" "TE HOGE STROOM BEVOCHTIGER" "BEVOCHTIGER DEFECT" "BEVOCHTIGER DEFECT" "VERVUILDE STOOMCILINDER" "RUIMTE TEMP. TE HOOG" "RUIMTE TEMP. TE LAAG" " VOCHTIGHEID TE HOOG" " VOCHTIGHEID TE LAAG" "RUIMTE TEMP. TE HOOG" "RUIMTE TEMP. TE LAAG" " VOCHTIGHEID TE HOOG" "VOCHTIGHEID TE LAAG " "DRAAIUREN UNIT OVERSCHREDEN" "DRAAIUREN COMPR. 1 OVERSCHREDEN" "DRAAIUREN BEVOCHTIGER OVERSCHREDEN" "PTC SENSOR DEFECT" "RUIMTE SENSOR DEFECT" "RUIMTE SENSOR DEFECT" "EEAP SENSOR DEFECT" "WATER BEWAKINGS SENSOR DEFECT " "NETWERK DEFECT" "GEEN GEHEUGEN" "UNIT AAN" "UNIT UIT" "SLAAP STAND" "STANDBY STAND" "SPANNING IN UNIT LOGIN" "SPANNING UIT" "Unit 1 ontkoppeld" "Unit 2 ontkoppeld " "Unit 3 ontkoppeld " "Unit 4 ontkoppeld " "Unit 5 ontkoppeld " "Unit 6 ontkoppeld " "Unit 7 ontkoppeld " "Unit 8 ontkoppeld " "Unit 9 ontkoppeld " "Unit 10 ontkoppeld "
Alarm Alarm (geprogr. Vertraging LPd) Waarschuwing(Vertraging 15 m) Waarschuwing (Vertraging 10s) Alarm (Vertraging 30s) Waarschuwing (Vertraging 10s, de verhitters, bevochtiging en ontvochtiging worden gestopt) Alarm (Vertraging 10s de unit stopt) Waarschuwing (Vertraging 10s) Waarschuwing (melding) Alarm (unit stopt) Waarschuwing (melding) Alarm (unit stopt) Waarschuwing (Vertraging 40m) Waarschuwing Waarschuwing (Vertraging 40m) Waarschuwing (Vertraging 40m) Waarschuwing Waarschuwing (Vertraging 15m) Waarschuwing (Vertraging 15m) Waarschuwing (Vertraging 15m) Waarschuwing (Vertraging 15m) Alarm (Vertraging 15m) Alarm (Vertraging 15m) Alarm (Vertraging 15m) Alarm (Vertraging 15m) Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Alarm Waarschuwing Waarschuwing Waarschuwing Waarschuwing Bericht Bericht Bericht Bericht Bericht Bericht Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing
MICROFACE CODE A52 A53 A54 A55 A56 A57 A58 A59 A60
MICROFACE BERICHT "HP2" "LP2" "HC2"
A61 A62 A63 A64
"Out" "gLy" -
A65 A66
"Fir" -
A67
-
A68
"UI2"
A69 A70 A71 A72 A73 A74 A75 A76 A77 A78 A79 A80 A81 A82 A83 A84 A85
"UI2" "nEt" "th1" "th2" "Fir" "FA1" "FA2" "Hb" "SId" "SU1" "SU2" "rSF" "rSF" "Out" "gLy" "SPO"
HIROMATIC BERICHT
Type
"Unit 11 ontkoppeld " "Unit 12 ontkoppeld " "Unit 13 ontkoppeld " "Unit 14 ontkoppeld " "Unit 15 ontkoppeld " "Unit 16 ontkoppeld " "COMPR. 2 HOGEDRUK" "COMPRESSOR 2 LAGEDRUK" "DRAAIUREN COMPR. 2 OVERSCHREDEN" "BUITEN TEMP. SENSOR" "GLYCOL TEMP. SENSOR" "FREECOOLING 1 UUR GESTOPT" "AAN-UIT NIET MOGELIJK DOOR HIROMATIC" "ROOK ALARM" "GEEN SPANNING (GEBRUIKERS INGANG)" "VOEDING AAN (GEBRUIKERS INGANG)" "GEBRUIKERS INGANG 2 INGESCHAKELD" "GEBRUIKERS INGANG GETRIGGERD "GEEN VERBINDING MET UNIT 1" "COMPRESSOR 1 MOTOR PROTECTIE" "COMPRESSOR 2 MOTOR PROTECTIE" "BRAND ALARM" "GEEN GEHEUGEN" "CONDENSER 1 VENT. DEFECT" "CONDENSER 2 VENT. DEFECT" "NETWERK PING" "SUBGROEP-ID NIET UNIEK" "SUBGROEP-UNIT 1 NIET VERBONDEN" "SUBGROEP-UNIT 2 NIET VERBONDEN" "GEDEELDE RUIMTE SENSOR DEFECT" "GEDEELDE RUIMTE SENSOR DEFECT" "GEDEELDE BUITENTEMP. SENSOR" "GEDEELDE GLYCOL TEMP. SENSOR" "UNIT SYNCHRONISATIE (=Korte Reset)"
Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Alarm Alarm Waarschuwing Waarschuwing Waarschuwing Bericht Bericht Alarm Bericht Bericht Waarschuwing Alarm Waarschuwing Alarm Alarm Alarm Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Waarschuwing Alarm Waarschuwing Waarschuwing Bericht
Parameters voor KPN units op Microface volgorde tussen haakjes FC optie 2/3 parameter Alarm t1 t2 H1 t3 t4 Act AcH EEt EEh H1L H1r H2L H2r dr Pin SPT SP2 SPH SUP FS nEt SHP CAS Std Aut rE HdE Pbt IF PBh IFH PH dHh dt1 dt2 dt3 stb rot Ht Lt HH LH HtA LtA HHA LHA LPd tHC US1 US2 Flo
tekst storingsmelding retourlucht temp PTC inblaastemp. retourlucht vocht buitentemp glycoltemp actueel setpoint temp actueel setpoint vocht externe temp voeler(alarm) externe vocht voeler(alarm) hirosensor 1 hirosensor 1 hirosensor 2 hirosensor 2 drain bevochtiging Pin code + enter setpoint temp setpoint temp 2 setpoint vocht setpoint min. Inblaas fanspeed verdamperfan aantal gekoppelde units shared parameters cascade regeling standaard instelling automatische herstart hiromatic aan/uit mogelijk dode band instelling proportionele band temp integratiefactor temp proportionele band vocht integratiefactor vocht bevochtiging aan/uit of prop. hysteresis ontvochtiging temp.verschil ruimte/buiten temp.verschil ruimte/glycol temp.verschil vrije koeling aantal standbye units compressor rotatie hoge temp melding lage temp melding hoge vocht melding lage temp melding hoge temp alarm lage temp alarm hoge vocht alarm lage vocht alarm lage druk overbrugging therm. Bev. Compressor gebruikers ingang 1 gebruikers ingang 2 lage luchtstroom
6GUA DX/FC uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uit/aan password 25 no no no(14) no 1 no no no 300 no 0 3 no 10 no ono 30 no(5) no(con) no(2) 0 no 30 10 no no no no no no 5 yes Alp nu 35
7GUA DX/FC uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uit/aan password 25 no no no(14) 75(100) 1 no no no 300 no 0 3 no 10 no ono 30 no(5) no(con) no(2) 0 no 30 10 no no no no no no 5 yes Alp Lsi 35
32/42UA DX/FC uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uitlezing uit/aan password 25 no no no(14) no 1 no no no 300 no 0 3 no 10 no ono 30 no(5) no(con) no(2) 0 no 30 10 no no no no no no 5 yes Alp Lsi 35
Parameters voor KPN units op Microface volgorde tussen haakjes FC optie 2/3 parameter FF Car typ AoP rt EHS AN1 AN2 AL6 PdO dEH dEC HU HS Pro LSt r1 r2 Flo L9 HUC Id CEN CA1 CA2 CA3 CA4 CA5 CA6 CA7 CA8 CA9 C10 C11
tekst
koelingtype openingstijd klepmotor aantal verhitter trappen analoge uitgang 1 analoge uitgang 2
ontvochtiging mogelijk ontvochtigingrelais model bevochtiging spanning bevochtiging stoomcapaciteit waterlekkage detector analoge uitgang 1 analoge uitgang 2 lage luchtstroom water lekkage detector amperage bevochtiging identificatienummer kalibratie humitemp temp kal.humitemp vocht kal. Inblaastemp. kal. EEAP kal. EEAP kal. Hirosensor 1 kal. Hirosensor 1 kal. Hirosensor 2 kal. Hirosensor 2 kal. PTC buitentemp kal. Glycoltemp
6GUA DX/FC Ahp no dFc 0% 170 0 3P1 3P2 AL1 no no A1 et .. no no uitlezing uitlezing uitlezing uitlezing uitlezing 1 yes ..(t1) ..(h1) t1(t2) .. .. .. .. .. .. (t3) ..
7GUA DX/FC Ahp no tdE(tFd) 0% 170 0 3P1 FS AL1 no no A1 21L 230 no no uitlezing uitlezing uitlezing uitlezing uitlezing 1 yes ..(t1) ..(h1) t1(t2) .. .. .. .. .. .. (t3) ..
32/42UA DX/FC Ahp no tdE/(tFd) 0% 170 0 3P1 3P2 AL1 no no A1 21L 230 no no uitlezing uitlezing uitlezing uitlezing uitlezing 1 yes t1 h1 .(t2). .. .. .. .. .. .. (t3) ..
opmerkingen: Wanneer DEC op A1, kan op 300/301/302 OH meldingen worden uitgelezen Inregelen van de optie 2/3 door gebruikmaking van de kalibratie van ruimtetemp en buitentemp. hierbij gebruik maken van password 4 Let op; wanneer bij vrije koeling de RT boven 27 C komt zal bij temperatuurdaling de vrije koeling pas na 1 uur terugschakelen De servomotoren lopen bij spanningsopkomst altijd eerst naar beide eindpunten( stelt zelf zijn slag in) Bij de 7GUA met optie 2/3 moet van de verdamperfanspeedcontrol de potmeter P3 (min velocity) op maximaal gezet worden( I.v.m.brandschakeling ventilatoren).
Liebert HIROSS S.p.A. Zona Industriale Tognana Via Leonardo da Vinci, 8 35028 Piove di Sacco (PD) ITALY TEL. +39.049.97.19.111 FAX +39.049.58.41.257 Internet: www.Liebert-HIROSS.com