DIAGRAM SATU GARIS GARDU INDUK DENAI TAMORA
SEI ROTAN
ACSR 2 × 240 mm2
ACSR 2 × 240 mm2
LA : 10 kA PT 150 kV/√3/100V/√3
LA : 10 kA
PT 150 kV/√3/100V/√3 LINE TRAP
LINE TRAP
ES
PMS 1250 A, 31,5 kA
CT: 1200/1 A M = 1200/1 A P = 1200/1 A
CT: 800/5 A M = 800/5 A P = 800/1 A
PMT 1250A 31,5 kA
PMT 3150A 31,5 kA PMS 1250 A, ..... kA
PMS 1250 A, ..... kA
BUS 150 kV, 2000A
BUS I
ES
PMS 1250 A, 31,5 kA
BUS II PMS 1250 A, 31,5 kA
PMS 1250 A, 31,5 kA
PMT 3150A 31,5 kA CT: 150 – 300 /1 A LA 65 kA
PAUWELS TD2 60 MVA
NGR: 12 ohm 1000 A
CT : 2000/5
P 2 PMT 20kV, 2000A, 25 kA PMS 2000 A, 62,5 kA
BUS I
BUS 20 kV, 2000A, MODALEK
INCOM
BUS 20 kV, 2000A, MERLIN GERIN
BUS II
PMT 2500 A
PMT 630 A
PMT 630 A
PMT 630 A
CT 2000/5 A
CT 600/5 A
CT 600/5 A
CT 600/5 A
LB PMT 800A 16 kA
Trafo PS 20kV/380220V
CT 600/5
200 kVA
PMT 800A 16 kA CT 600/5
PMT 800A 16 kA CT 600/5
PMT 800A 25 kA CT 800/5
PMT 800A 25 kA CT 800/5
PMT 800A 25 kA CT 800/5
Kopel BUS KANGURU DA-6
KOALA DA-5
KUS KUS DA-4
ANOA DA-3
TAPIR DA-2
CT 600/5 A
BUSTIE CT 2000/5
PS
PMT 630 A
PT 20 kV/√3/ 100V/√3
PT 20 kV/√3/ 100V/√3
DN1
DN2
PANDA DA-1
Universitas Sumatera Utara
DN3
D
Lampiran 2 LAPORAN HASIL PENGUKURAN TAHANAN PENTANAHAN KAKI MENARA GARDU INDUK : SEI ROTAN SEGMENT
: SEI ROTAN-TEBING TINGGI
NO TOWER
HASIL UKUR PENTANAHAN KAKI TOWER (OHM)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
3.2 7.2 3.9 5.7 6.6 8.3 5.8 3 6.3 5.4 5.4 4.2 4.2 6.2 7.1 4.3 7.2 6.3 7.3 8.4 8.3 8.8 9.7 7.5 8.6 7.2 9.2 8.2 5.8 8.2 7.3 8.8 5.5 5.7 8.7 7.7 6.5 6.8 5.9 8.1 9.3 7.8 7.2 8.4 8.8 6.8 6.4 6.8 7.8 7.4
2.1 5.2 4.2 7.9 5.3 8.3 6.4 3.2 6.2 5.5 7.6 4.2 4.4 5.2 7.2 3.4 7.2 6.3 7.4 8.3 8.5 8.4 9.8 7.4 6.4 8.9 9.4 8.4 7.8 8.1 8.3 8.7 5.9 5.9 8.6 7.9 6.2 6.9 6 8.2 8.1 7.4 7.3 8.4 8.9 7.3 6.6 6.1 8.8 7.9
4.2 3.5 2.9 6.3 5.4 8.2 4.2 3.1 5.1 6.2 8.6 3.7 4.2 6.2 6.2 2.9 7.3 6.3 7.3 7.8 8.3 8.2 9.3 7.5 7.5 8.3 9.5 8.8 6.5 8.8 8.2 9.7 5.2 5.8 8.7 8.8 6.1 6.6 6.4 8.3 8.3 7.4 7.3 8.7 8.3 7.3 5.5 6.2 7.4 6.8
1.9 5.5 4.2 6.1 6.7 8.7 4.4 3.1 5.6 4.7 6.9 6.5 3.8 6.2 6.9 3.6 6.5 6.2 7.4 8.2 8.5 7.3 9.2 7.2 7.3 8.5 9.5 8.6 6.9 8.1 8.2 9.7 5.2 5.8 8.5 8.8 6..1 6.9 6.11 8.5 8.9 7.4 7.8 8.5 8.5 7.2 6.5 5.7 7.4 6.8
LOKASI
KETERANGAN
dipasang ground langsung di kaki D
dipasang ground langsung di kaki D dipasang ground langsung di kaki D
dipasang ground langsung di kaki D
dipasang ground langsung di kaki D
dipasang ground langsung di kaki A dan C
Universitas Sumatera Utara
Lanjutan Lampiran 2
NO TOWER 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100
HASIL UKUR PENTANAHAN KAKI TOWER (OHM) 8.2 5.3 5.9 7.9 7.8 6.5 7.5 5.7 9.8 9.8 8.8 9.1 8.3 7.2 7.3 8.9 7.9 7.2 6.2 6.3 5.6 7.2 7.4 7.2 5.7 4.7 11 4 8.9 7.4 5.4 8 3.7 6 7 4.5 3.5 9 5 5 7.9 5.8 2.4 4.2 6.8 3.9 3.4 3.2 3.6 8.6
7.2 5.4 5.9 7.4 7.9 6.5 7.5 5.9 8.9 9.5 8.8 9.5 8.2 7.2 7.5 9.2 8.4 7.8 5.4 6.8 6.4 7.3 7.5 7.6 4.7 7.3 6.4 6.6 9 6.2 4.4 8 5.4 6.4 4.8 5.1 3.3 8.5 2.2 4.6 8.4 5.6 3.6 2.2 6.2 4.8 6.4 3.6 8.4 8.4
7.6 5.4 5.8 7.8 8.1 6.5 7.5 5.8 8.9 7.9 9.2 9.1 8.3 7.2 7.5 9 8.3 6.8 4.3 6.3 8.5 7.4 7.5 7.6 6.3 6.3 8.4 5.6 9 7 8 6 6.3 4.4 5 4.1 5 9.5 5.2 3.3 7.8 5.8 3.2 3.6 7.3 4.4 5.8 2.2 8.5 8.2
7.6 5.5 5.7 8.9 8.2 6.6 7.8 5.9 9.2 7.9 9.4 9.1 8.2 7.3 7.5 8.7 8.4 6.3 3.1 6.8 7.5 6.9 7.7 7.5 7.3 5.7 9 5 9.1 6.6 7 6 6 6.2 7.2 4.7 4.8 9.3 5.2 4.3 8.2 3.6 4.8 5.8 4.7 5.6 4.9 4.6 7.6 8.2
LOKASI
KETERANGAN
dipasang ground langsung di kaki D
dipasang ground langsung di kaki B dan D
dipasang ground langsung di kaki B dan D dipasang ground langsung di kaki B
dipasang ground langsung di kaki D dipasang ground langsung di kaki C dipasang ground langsung di kaki D
dipasang ground langsung di kaki D dipasang ground langsung di kaki D dipasang ground langsung di kaki D
dipasang ground langsung di kaki D dipasang ground langsung di kaki D dipasang ground langsung di kaki D dipasang ground langsung di kaki D dipasang ground langsung di kaki C
Universitas Sumatera Utara
Lanjutan Lampiran 2
NO TOWER 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148
HASIL UKUR PENTANAHAN KAKI TOWER (OHM) 4.8 6.5 8.4 8.2 3.9 7.2 8.6 5.8 7.4 4.8 5.2 8.2 8.4 8.4 7.6 6 6.2 5.4 5.4 5.2 3.5 3 3 5.5 3.5 6 5.8 9 5.8 7.5 8.2 6.8 6.4 5.8 4.4 5.8 4.4 5.6 6.5 6.6 7.8 6.4 3 8.2 8.5 5.5 6.4 3.2
5.8 6.2 8.4 7.8 4.3 7.5 6.6 4.2 7 7.6 7.4 8.4 8.4 7.9 6 6 5.2 4.9 4.2 9.8 4.5 4 3.5 4.8 4 5 6.4 9.2 5 8.8 7.8 6.2 6..6 5.2 4.6 5.6 4 6 7.3 6.9 7.6 6.8 3.4 8.4 8.2 5.6 6.2 4.2
5.6 5.7 8.4 7.8 4.8 6.7 8.8 4.4 5.4 8.4 5.4 8.4 7.8 8.6 5.6 4.8 6.2 4.4 4.6 8.6 3.8 3.2 3 4.5 3.8 5.2 6.2 7.8 8 5.2 7.6 6.3 6.5 5 4 5 3.8 4.4 6.8 7 7.2 6.2 2.8 8.1 7.3 5.8 6.2 4.6
5.7 6.2 8.4 8.2 4.8 7.6 8.2 3.6 3 8.4 7.2 8.2 8.6 8.8 6 6.2 6 5.3 6 8.4 4.2 3.8 3.5 5.2 4.7 5.8 6.6 7 7.3 5.5 9.4 6.3 6.1 5 4.4 5.6 5.6 5.2 6.9 6.7 7.8 7 3.6 8.2 7.9 5.5 6 4.4
LOKASI
KETERANGAN
dipasang ground langsung di kaki D
dipasang ground langsung di kaki D dipasang ground langsung di kaki D dipasang ground langsung di kaki D dipasang ground langsung di kaki D dipasang ground langsung di kaki D
dipasang ground langsung di kaki D dipasang ground langsung di kaki D
dipasang ground langsung di kaki D dipasang ground langsung di kaki D
dipasang ground langsung di kaki D
dipasang ground langsung di kaki D
Dari Laporan Pengukuran Tahanan Pentanahan Kaki Menara, maka diperoleh ratarata tahanan kaki menara yang diperoleh adalah sekitar 8 ohm.
Universitas Sumatera Utara
Lampiran 3 LAPORAN KONDISI (TRIP/LEPAS/MASUK) PMT 150 kV TRANSMISI SEI ROTAN – TEBING TINGGI, Tahun 2005 GARDU INDUK : SEI ROTAN SEGMENT Bulan Januari Februari Maret April Mei Juni Juli
Agustus
: SEI ROTAN-TEBING TINGGI Nama Gardu Induk (GI)
PMT TRIP
Uraian gangguan Trip Normal TGL PKL TGL PKL
A
PADAM
Indikasi yang muncul Penyebab
Menit
kWH
Annuciator
M
S.Rotan
Pht.arah TT
31
17.55
31
A
Dist.relay zone 1 phase T
17.55
September
S.Rotan T.Tinggi
Pht.arah TT Pht.arah SR
04
16.50
04
16.50 16.50
Main protect. AR in progess
Oktober
S.Rotan T.Tinggi
Pht.arah TT Pht.arah SR
02
04.15
02
04.15
Main protect. AR in progess
November Desember
Rele
A
Diduga surja petir
Dist.relay zone 1 phase S. Dist.relay zone 1 phase S
Dist.relay zone 1 phase S Dist.relay zone 1 pahse S
Diduga ada isolator yang flashover akibat surja petir
M
A
Universitas Sumatera Utara
Lampiran 4 LAPORAN KONDISI (TRIP/LEPAS/MASUK) PMT 150 kV TRANSMISI SEI ROTAN - TEBING TINGGI, Tahun 2006 GARDU INDUK : SEI ROTAN SEGMENT Bulan
: SEI ROTAN-TEBING TINGGI Nama Gardu Induk (GI)
PMT TRIP
Uraian gangguan Trip Normal TGL PKL TGL PKL
Januari Februari Maret April
Mei
S.Rotan T.Tinggi
Pht.arah TT Pht.arah SR
Pht.arah TT Pht.arah SR
10
15.57
01
16.02 16.04
03.29
10
S.Rotan S.Rotan
Pht.arah TT Pht.arah TT
01 19
Rele
16.42 13.45
A Main protec, AR inprogess TP fail
5 6
M
03.29
A
September
Annuciator
M
01
Agustus
Oktober
kWH
A S.Rotan T.Tinggi
Indikasi yang muncul Penyebab
Menit
A
Juni Juli
PADAM
Dist. Relay zone 1phase T
Main protec, AR in progess
A Dist.zone 1 phase T
Main protec, AR in progess
Dist.zone 1 phase T
M 01 19
S.Rotan S.Rotan
Pht.arah TT Pht.arah TT
19
00.52 01.58
19
00.52 02.01
Desember
S.Rotan
Pht.arah TT
20
05.02
19
05.16
M s d m (
N
A Dist.zone 1 phase T Dist.zone 1 phase T
16.42 13.45
November
Di duga terjadi flashover pd isolator, Pht 150 kV SR-TT
Dist.zone 1 phase S Dist.zone 1 phase R,S
Distance Protection
Dist.zone 1 phase R,S,T
Universitas Sumatera Utara
T d p y T p –
Lampiran 5 LAPORAN KONDISI (TRIP/LEPAS/MASUK) PMT 150 kV TRANSMISI SEI ROTAN - TEBING TINGGI, Tahun 2007 GARDU INDUK : SEI ROTAN SEGMENT
: SEI ROTAN-TEBING TINGGI
Uraian Kejadian
PMT Trip/Lepas/Tidak Kondisi TGL PKL
Proses Pemulihan
Beban Sebelum Kejadian kV Amp MW MVAR
PMT
TGL
A 15
08.14
145
320
kWh.PADAM
PKL
ADA Menit Jlh.kWH
TIDAK ADA
M 80
-8
15
A
Idikator Annuciator Muncul
Rele yang bekerja Indikasi muncul/ kode rele
A
18.00
406
1.218.000
-
N -
M
-
N
-
-
-
-
Mekanik fasa S, macet
-
8
9
15.06
-
-
-
-
-
60
12
10
10.22
111
111.000
-
-
-
230
58
12
01
18.06
-
-
-
-
-
290
72
8
11
19.10
5
-
-
RY – Z1 Ф B main protect, AR inprogress , recloser bekerja
03.09
155
270
68
4
9
08.03
150
320
80
10
08.31
150
240
01
18.00
148
11
19.05
100
-
A
A
HAR 5 tahun, pembersihan isolator
A
-
30
Penyebab Kejadian
M
M
A
A
Cuaca mendung macet, dugaan surja petir Perbaikan mekanik PMT di GI S.Rotan
N Penggantian timer relay discrepancy Ada jumperan konduktor ang putus
-
-
N
Universitas Sumatera Utara
Lampiran 6 LAPORAN KONDISI (TRIP/LEPAS/MASUK) PMT 150 kV TRANSMISI SEI ROTAN - TEBING TINGGI, Tahun 2008 GARDU INDUK : SEI ROTAN SEGMENT
: SEI ROTAN-TEBING TINGGI
Uraian Kegiatan PMT Trip/Lepas/Tidak Beban Sebelum Kejadian Kondisi TGL PKL kV Amp MW MVAR 14 10.49 151 335 84 12
Proses Pemulihan PMT
TGL 14
PKL 14.09
A 18
13.34
150
228
72
-16
29
11.17
151
335
84
12
M 18
13.53
29
11.22
A 11
16.42
149
320
80
12
22 23 25 27 28 29 21
09.35 08.13 10.16 08.30 09.20 08.00 09.14
150 147 149 148 150 150 148
480 390 290 270 385 415 495
120 98 72 68 96 104 124
8 4 14 16 16 8 4
7
08.52
150
370
92
03
16.39
150
385
96
kWh.PADAM ADA TIDAK ADA Menit Jlh.kWH 190 149125 19
18955
5
7000
-
-
-
22 23 25 27 28 29 21
16.19 16.19 16.45 15.34 16.04 16.35 16.14
404 486 389 433 404 465 420
671758 656585 390785 404988 538806 192975 720186
12
7
10.57
123
12
03
16.47
8
A
A
-
-
Main protec, TP fail Main protection
Perbaikan kabel
Distance zone 1 Ø B,C. A/R inprogress, MFRF -
Cuaca di S.Rotan/ hujan petir Test SCADA
-
Cuaca hujan petir
-
-
-
Penambahan isolator Penambahan isolator Penambahan isolator Penambahan isolator Penambahan isolator Penambahan isolator Penggantian isolator
157651
-
-
10669
-
-
Perbaikan Pans Bus-2
Main protec
-
-
A
M
-
N -
M
Penyebab Kejadian
N
A -
Rele yang bekerja Indikasi muncul/ kode rele
-
A
M -
Idikator Annuciator Muncul
N
A
N
Universitas Sumatera Utara
Lampiran 7 LAPORAN KONDISI (TRIP/LEPAS/MASUK) PMT 150 kV TRANSMISI SEI ROTAN - TEBING TINGGI, Tahun 2009 GARDU INDUK : SEI ROTAN SEGMENT
: SEI ROTAN-TEBING TINGGI
Uraian Kegiatan
PMT Trip/Lepas/Tidak Kondisi TGL PKL
kV
Proses Pemulihan
Beban Sebelum Kejadian Amp MW MVAR
PMT
TGL
PKL
10
13.58
A 10
07.59
150
130
32
kWh.PADAM
Menit
ADA Jlh.kWH
TIDAK ADA
M 4
A
Idikator Annuciator Muncul
Rele yang bekerja Indikasi muncul/ kode rele
-
-
A 479
215789
Penyebab Kejadian
N
-
M
HAR (Pemeliharaan tahunan)
A
N
26
10.08
149
225
56
14
26
10.53
45
34799
-
-
-
Melepas cup line trap
7
09.35
149
112
28
4
7
16.22
407
156669
-
-
-
8
10.32
148
305
76
12
8
15.05
316
329236
-
-
-
Pemasangan LA di tower 25 & 75 Pemasangan LA di tower 112 & 133
A
M
A
N
Universitas Sumatera Utara