Building Air Leakage Test Results In Compliance with European Norm EN13829 EPB lipa BVBA
EPB-EAP-veiligheid-EPC publieke-PHPP-blower door http://www.epblipa.be -
[email protected]
Patrick Brants-Lien Van Droogenbroeck Varenbergstraat 33 * 9200 Oudegem T/F (052) 33 55 87 * GSM (0486) 02 81 20 Rek. BIC ARSPBE22 / BE 63 9797 8865 8808 BTW 0832.896.339 VEA nr EP12862 EP12862
Building Details Building Address: Kantoor EPB Lipa Woning Liesbet Van Droogenbroeck Oude Baan 3 bus 1 en 2 9200 Dendermonde Test technician: Patrick Brants Varenbergstraat 33 9200 Dendermonde Test company: EPB Lipa BVBA
Elevation: Height above ground: Building Volume, V: Total envelope area, AT BAT Building exposure to wind: building Accuracy of measurements:
6m 11 m 730,8 m³ 0 m² Partially protected 100%
Testing Details Fan Model: Retrotec 2000
Fan SN: FT3000253
Gauge Model: DM-2
Gauge SN: 203247
Depressurize set Date: 2014-03-16 Time: 10h45 to 11h15
Environmental Conditions: Barometric Pressure: 102,1 KPa from Direct measurement. Wind speed:
3: Gentle breeze
Temperature:
Initial: indoors 20 °C outdoors 10 °C. Final: indoors 20 °C outdoors 11 °C.
Test Data: 10 bias pressures taken for 10 sec each. 10 induced pressures taken for 20 sec each. Bias, initial [Pa] Induced Pressure [Pa] Bias, final[Pa] Door Fan Pressure, [Pa] Total flow, Vr
-0,32
Corrected flow, Venv
-15,0
-20,0
-25,0
-30,0
-35,0
-40,0
-45,0
-50,0
-55,0
-60,0
-65,0
-70,0
144
182
212
242
275
304
355
386
426
458
481
515
144,0
182,0
212,0
242,0
275,0
355,0
458,0
481,0
515,0
175,3
204,2
233,1
264,9
342,0
386, 0 371,8
426,0
138,7
304, 0 292,8
410,4
441,2
463,4
496,1
4,1% 2,2% Error [%] Bias pressure Averages:
-1,6%
-3,8%
-3,9%
-5,0%
0,7%
0,4%
2,4%
2,5%
0,8%
1,6%
-2,80
[m3/h]
[m3/h]
initial [Pa] ∆P01 -0,32, ∆P01- -0,32, ∆P01+ 0,00 final [Pa] ∆P01 -2,80, ∆P01- -2,80, ∆P01+ 0,00
Building Gauge Pressure
Building Gauge Pressure vs. Flow
Depressurize Test Results Results
Results
Correlation, r
99,74
Intercept, Cenv
16,75
14,45
19,45
Intercept, CL
16,906
14,60
19,60
Air flow at 50 Pa, V50 [m3/h] Air changes at 50 Pa, n50 [/h] Permeability at 50 Pa, v50 [m3/h.m2]
Slope, n
0,7978
0,7573
0,8383
Specific Leakage at 50 Pa, w50
[%]
[m3/h.Pan] [m3/h.Pan]
95% confidence limits
95% confidence
Uncertainty
383,0
374,5
392,5
+/-2,4%
0,5245
0,0001
1,050
+/-100,0%
[m3/h.m2]
Pressurize set Date: 2014-03-16 Time: 11h20 to 11h45
Environmental Conditions: Barometric Pressure: 102,1 KPa from Direct measurement. Wind speed:
3: Gentle breeze
Temperature:
Initial: indoors 20 °C outdoors 11 °C. Final: indoors 20 °C outdoors 11 °C.
Test Data: 10 bias pressures taken for 10 sec each. 10 induced pressures taken for 20 sec each. Bias, initial [Pa] Induced Pressure [Pa] Bias, final[Pa] Door Fan pressure, [Pa] Total flow, Vr
-2,89
15,0
20,0
25,0
30,0
35,0
40,0
45,0
50,0
55,0
60,0
65,0
70,0
145
183
214
280
300
340
363
390
423
453
482
505
145,0
183,0
214,0
280,0
300,0
340,0
363,0
390,0
423,0
453,0
482,0
505,0
Corrected flow, Venv
146,6
185,1
216,4
283,1
303,4
343,8
367,1
394,4
427,7
458,1
487,4
510,7
Error [%]
-3,1%
-1,9%
-3,8%
8,7%
2,7%
4,3%
0,9%
-0,7%
-0,6%
-1,0%
-1,6%
-3,2%
-2,30
[m3/h]
[m3/h]
Bias pressure Averages:
initial [Pa] ∆P01 -2,89, ∆P01- -2,89, ∆P01+ 0,00 final [Pa] ∆P01 -2,30, ∆P01- -2,30, ∆P01+ 0,00
Building Gauge Pressure
Building Gauge Pressure vs. Flow
Pressurize Test Results Results
Correlation, r
99,61
Intercept, Cenv
12,10
9,825
14,90
Intercept, CL
12,102
9,835
14,90
Air flow at 50 Pa, V50 [m3/h] Air changes at 50 Pa, n50 [/h] Permeability at 50 Pa, v50 [m3/h.m2]
Slope, n
0,8812
0,8259
0,9366
Specific Leakage at 50 Pa, w50
[%]
[m3/h.Pan] [m3/h.Pan]
95% confidence
Results
95% confidence limits
Uncertainty
380,0
370,5
390,5
+/-2,6%
0,5200
0,0001
1,041
+/-100,0%
[m3/h.m2]
Combined Test Data Results
95% Confidence Interval
Uncertainty
Air flow at 50 Pa, V50 [m3/h]
381,5
372,5
391,5
+/-2,5%
Air changes at 50 Pa, n50 [/h]
0,5225
0,0001
1,045
+/-100,0%
Permeability at 50 Pa, v50 [m3/h.m2] Specific Leakage at 50 Pa, w50
[m3/h.m2]
VOOR AKKOORD,
Patrick Brants
+/-2,5%
Test Notes: Blowerdoortoestel is opgesteld in de inkomdeur gebouw en digitale manometer is opgesteld in de vergaderzaal van het gelijkvloers. Beide D-systemen zijn afgesloten aan de inen uitgang van het gebouw met een ballon, geen CV-ketels en geen recirculatiedampkappen. Test is uitgevoerd conform methode A van de norm, verliesoppervlakte bepaald conform EPB decreet, door EPB-verslaggever EPB Lipa bvba. Voor de plannen waarop de berekening is gemaakt, verwijzen wij ook naar de EPB-studie. De te meten zone omvat de volledige
buitenschil van het gebouw. Alle binnendeuren zijn geopend, met uitzondering van de deuren naar de toiletten. "Bij de luchtdichtheidsmeting werden alle voorschriften in het kader van de EPB-regelgeving zoals beschreven in het "specificatiedocument, versie 1 dd 20.10.2010 gerespecteerd", als ook bijlage 5 dd 17.12.2012 aangaande de bijkomende specificaties aangaande luchtdichtheid zijn gerespecteerd. (zie ww.epbd.be/go/luchtdichtheidsmeting)” Het binnenvolume is bepaald conform de norm en conform de regels opgesteld door PHP Opmerking: het gebouw behaalt een uitstekend resultaat. Voorafgaand aan deze meting waren er ook reeds 2 metingen methode B uitgevoerd om te kijken welk resultaat haalbaar kon zijn. Deze test toont aan dat ook zonder slabben aan de ramen een voortreffelijk resultaat kan worden behaald. Bij de rondgang in de woning zijn er nergens noemenswaardige lekken of luchtstromen geconstateerd.
Foto’s van opstelling:
Foto’s afsluiten D-systeem:
Foto’s DM2A tijdens test:
Calibration Certificate Retrotec 2000 . Range
N
K
K1
K2
K3
K4
Open(22)
0,5214
519,618
-0,07
0,8
-0,115
1
A
0,503
264,996
-0,075
1
0
1
B
0,5
174,8824
0
0,3
0
1
C8
0,5
78,5
-0,02
0,5
0,016
1
C6
0,505
61,3
0,054
0,5
0,004
1
C4
0,5077
42
0,009
0,5
0,0009
1
C2
0,52
22
0,11
0,5
-0,001
1
C1
0,541
11,9239
0,13
0,4
-0,0014
1
L4
0,48
4,0995
0,003
1
0,0004
1
L2
0,502
2,0678
0
0,5
0,0001
1
L1
0,4925
1,1614
0,1
0,5
0,0001
1