MONTÁŽE ČAKOVICEs.r.o.
Přenos a zpracování dat zařízeními SEL Montáže Čakovice s.r.o. (Igor Botlík)
strana 1
Použití SEL 2505/6, 2515/6, 2594/5 Náhrada přímého propojení DI IED 1 DO1 DO2 ….. DO8 DI1 DI2 ….. DI8
MONTÁŽE ČAKOVICEs.r.o.
DO IED 2
0
1
1
0
0
1
1
0
0
1
1
0
DI1 DI2 ….. DI8 DO1 DO2 ….. DO8
NE! (při větších vzdálenostech) strana 2
Zařízení SEL pro přenos stavů Connected Device
Protocol
MONTÁŽE ČAKOVICEs.r.o.
Surface Rack Mount Mount
SEL-2505 or SEL-2506 Remote SEL MIRRORED BITS® SEL-2505 SEL-2506 8I/O Module, Relay, or SEL-2100 Communications Logic Processor SEL-2594 Contact Transfer 8I/O Module or SEL-2595 Teleprotection Terminal Through Multiplexers
IEEE C37.94
SEL-2411 PAC
SEL MIRRORED BITS® Communications
SEL-2440 DPAC
….
SEL-2594 SEL-2595
-
-
ano
ano
strana 3
MONTÁŽE ČAKOVICEs.r.o.
Použití SEL 2505/6, 2594/5 Nastavení SEL 2505/6
FIBER OPTIC
CONTROL SWITCHES ON OFF
TX
RX
10 9 PROTOCOL/BAUD = MB8/38400 = MB8/19200 = MB8/9600 = RESERVED
10 9 8 7 6 5 4 3 2 1 8 7&8
7 6 5 5&6 3&4 1&2
4 3 RX_ADD
2 1 TX_ADD
OUTPUT CONTACT MODE
=1
=1
=2
=2
=3
=3
=4
=4
SECURE FAST
190-2911-02
strana 4
Peer-to-Peer
MONTÁŽE ČAKOVICEs.r.o.
MIRRORED BITS® Jednoduchá a bezpečná metoda přenosu log. stavů mezi zařízeními Komunikace přes různá media Optické vlákno Multiplexní digitální síť Analogové modemy Rádiová síť (point-to-point)
Univerzální použití Implementace (využitím SEL HW) ve všech SEL zař. Low-cost řešení strana 5
MIRRORED BITS®
MONTÁŽE ČAKOVICEs.r.o.
Možnost vysílat a přijímat MB na dvou portech Monitorování jednotlivých stavů, events protokol výpadků pomocí příkazu „COMM“, buffer 255 záznamů, nastavení loop-back pro testování,… Možnost přímého datového propojení 2 komunikačně nekompatibilních zařízení či zařízení bez komunikace Zpracování pomocí logického enginu IEC 61131 Rychlost až 38.400 bps (transportní zpoždění typ. 4,2ms), plně duplexní, sériová asynchronní komunikace, cyklické 4B telegramy strana 6
MIRRORED BITS® v zařízeních SEL
MONTÁŽE ČAKOVICEs.r.o.
Využití protokolu i pro více IED
strana 7
MIRRORED BITS®
MONTÁŽE ČAKOVICEs.r.o.
Nastavení
strana 8
Použití SEL 2505/6, 2515/6, 2594/5
MONTÁŽE ČAKOVICEs.r.o.
Přímý přenos single/MM optikou
NonMIRRORED BITS Relay
NonSEL-2505 Contact I/O
RX
TX
TX
RX
Single-Mode Fiber Link Up to 80 km
SEL-2505
MIRRORED BITS Relay
Contact I/O
strana 9
MONTÁŽE ČAKOVICEs.r.o.
Použití SEL 2505/6, 2515/6, 2594/5
Přenos přes multiplexer ICON protokolem IEEE C37.94 SONET Multiplexer
SONET Multiplexer
ICON
Fiber Link SEL-2594 Contact I/O Non-MIRRORED BITS Relay
SEL-2594 Contact I/O Non-MIRRORED BITS Relay
SONET Multiplexer
SONET Multiplexer
SEL-2800
SEL-2800 Fiber Link
SEL-2505 Contact I/O Non-MIRRORED BITS Relay
SEL-2505 Contact I/O Non-MIRRORED BITS Relay
strana 10
Použití SEL 2505/6, 2515/6, 2594/5
MONTÁŽE ČAKOVICEs.r.o.
Kombinovaná zapojení SCADA 1)
IEC 61850
MIRRORED BITS Relay
IEC 61850 GOOSE
MIRRORED BITS Relay
MIRRORED BITS
Non-MIRRORED BITS Relay
Contact I/O
SEL2505
Contact I/O
Non-MIRRORED BITS Relay
SCADA 2)
IEC 61850
Non-MIRRORED BITS Relay
IEC 61850 GOOSE
SEL2505
MIRRORED BITS
MIRRORED BITS Relay
strana 11
Použití SEL 2505/6, 2515/6, 2594/5
MONTÁŽE ČAKOVICEs.r.o.
Kombinované zapojení se SEL- 2411 PAC SCADA IEC 61850
Non-MIRRORED BITS Relay
IEC 61850 GOOSE
Non-MIRRORED BITS Relay
IEC 61850 GOOSE
SEL-2411
3)
MIRRORED BITS
SEL2505
Contact I/O
Non-MIRRORED BITS Relay
strana 12
Implement Fast, Reliable Automation Apply the Rugged SEL-2411 Programmable Automation Controller
Withstands Extreme Conditions
Flexible – Install Up to Four SELECT™ I/O Cards
Match Your Application With SELECT I/O Cards SELECT I/O Card Designation
Maximum Cards Per SEL-2411
8 AI
4
4 AI / 4 AO
2
8 Digital Inputs
8 DI
4
8 Digital Outputs
8 DO
4
4 Digital Inputs / 4 Digital Outputs
4 DI / 4 DO
4
4 AC Current Inputs
4 ACI
1
Three-Phase AC Voltage Inputs
3 AVI
1
Card Description 8 Analog Inputs 4 Analog Inputs / 4 Analog Outputs
EIA-232 or EIA-485 Port EIA-232 / -485
1
Additional Key Benefits Quickly set and commission with ACSELERATOR® QuickSet SEL-5030 Software SER, DFR Implement distributed high-speed logic schemes with SEL MIRRORED BITS® communications links Communicate via Ethernet with Telnet, FTP, Modbus® TCP, and DNP3 LAN / WAN
Quickly Set With ACSELERATOR QuickSet Software
Application Example: Breaker Monitoring, Status Panel, and Transducers
Application Example: Ethernet Network Connection to DCS or SCADA DCS or SCADA Master
Ethernet Switch
Application Example: EIA-485 Multidrop Connection to DCS or SCADA DCS or SCADA Master
Diagnose System Problems With SER Time-tag changes of DI to nearest millisecond SER is important and useful Analyze system disturbances Understand sequence to understand problems Coordinate with time-tagged oscillographic or digital fault recorder (DFR) records
Station-wide / system-wide SER reporting DNP3 serial or LAN / WAN messages SEL Fast Messages to SEL-2032 Communications Processor or SEL-3351 System Computing Platform
Example SER Report Time-Tagged to Nearest Millisecond
Point Description
Data Source / Location
New State
Element Name
Implement Local Automatic Control LCD Display Pushbuttons
32 latch bits 64 SELOGIC variables and timers 32 front-panel display points 32 local bits for front-panel controls
LED Indicators
UserConfigurable Labels
32 remote bits for remote control
Install AC Voltage Input Card and Activate Built-In Functions VAB, VBC, VCA or VAN, VBN, VCN, VG magnitudes (V), and phase angles (degrees) Negative-sequence (3V2)
S E L -2 4 1 1
Example applications
System frequency (Hz)
Undervoltage or underfrequency load shedding
Event reports
Voltage control
Install AC Current Input Card and Activate Built-In Functions Line currents IA, IB, IC, and IN magnitudes (A), and phase angles (deg) IG (Residual Ground Fault Current) magnitude (A) and phase angle (deg) Negative-sequence current (3I2) magnitude System frequency (Hz) Event reports
S E L -2 4 1 1
Example applications Fault recording Underfrequency load shedding Protection backup
Install Both AC Current and Voltage Input Cards for Built-In Functions All of the voltage and current functions Real power (kW) Reactive power (kVAR) Apparent power (kVA) Power factor
S E L -2 4 1 1
Example applications VAR control SCADA data PF control Fault recording
AC Input Oscillograph
SEL-2411 Summary Base unit has 3 DO, 2 DI, and 4 card slots Flexible SELECT I/O cards provide many options 37 I/O points maximum per SEL-2411 Many protocol options
SEL-2411 Summary Best temperature, vibration, and electrical withstand capabilities Highest reliability Lowest overall cost SEL worldwide, ten-year product warranty
SEL DPAC
MONTÁŽE ČAKOVICEs.r.o.
$960 for 48 utility-grade I/O points = $20 point Microsecond timing Fast and powerful processing Flexible communications and protocols
strana 31
DPAC - robustní provedení I/O a mnohem více!
MONTÁŽE ČAKOVICEs.r.o.
Vysoká spolehlivost a robustní konstrukce Kritická hlášení Flexibilní digitální I / O výběr Běží v extrémních podmínkách Pohodlné na údržbu a podporu Jednoduché uvedení do provozu Jednoduché programování SEL Logic Použití i jako samostatný kontroler nebo SER (DFR) pro různé aplikace strana 32
Withstands Extreme Conditions
Designed, built, and tested to meet mission-critical IEEE and IEC protective relay standards for substations
DPAC Functional Block Diagram
New Features
• 64 SELOGIC® control equation variables • SNTP time synchronization • 5 DNP3 sessions • 2 Modbus® sessions
Flexible I/O Configuration to Match Your Needs • Available I/O configurations ♦
32 DI and 16 DO
♦
16 DI and 32 standard DO
♦
16 DI, 16 standard DO, and 16 high-current DO
♦
48 DI
• Digital inputs support ac or dc control signals • Digital input debounce settings
Mounting Options
Rack
Panel
Surface
DIN Rail
Diagnose System Problems With SER • Time-tag DI changes to nearest microsecond • SER is important and useful ♦
Analyze system disturbances
♦
Understand sequence to understand problems
♦
Coordinate with DFR records
• Station-wide / system-wide SER reporting ♦
DNP3 serial or LAN / WAN messages
♦
SEL Fast Messages to SEL-2032 or SEL-3530
Implement Local Automatic Control SELOGIC Control Equation Functions • 32 SELOGIC math variables (MVs) • 64 SELOGIC variables (SVs and SVTs) • 32 local bits • 32 remote bits • 32 nonvolatile latch bits • 32 up / down counters • 128 remote analog points
Flexible Connectivity for Complete Integration • Dual Ethernet ports (copper RJ45 or fiber LC) • Integrated Ethernet switch, which allows daisy chaining or redundancy • Dual serial ports ♦
Single EIA-232
♦
Single EIA-232, EIA-485, or fiber-optic V-pin or ST® connectors
Serial (Copper or Fiber) Communications Protocols • SEL ASCII, Fast Meter, Fast Operate, Fast Message, Fast SER • SEL MIRRORED BITS® communications • Compressed ASCII • SEL Messenger Points for SEL-3010 Event Messenger • Modbus RTU • DNP3
Dual Ethernet (Copper or Fiber) Communications Protocols • Modbus TCP • FTP, Telnet, Ping • DNP3 LAN / WAN • IEC 61850 (optional)
Quickly Set With ACSELERATOR QuickSet® SEL-5030 Software
Program With Standard Logic Gates Using the Graphical Logic Editor
DPAC Summary • Lowest overall cost for 48 I/O points • Many protocol options • Highest reliability • Detailed analysis with SER • SEL worldwide, 10-year product warranty
MONTÁŽE ČAKOVICEs.r.o.
Děkuji za pozornost.
strana 46