DAFTAR PUSTAKA [1]
-, L90 Line Current Differential System UR Series Instruction Manual rev. 6.0x, GE Digital Energy, Canada, 2015.
[2]
-, SPLN T5.002-1:2010, Pola Proteksi Saluran Transmisi, Bagian 1: Tegangan Tinggi 66 kV dan 150 kV, Badan Penerbit PLN, Jakarta, 2010.
[3]
-, SPLN T5.002-2:2010, Pola Proteksi Saluran Transmisi, Bagian 2: Tegangan Ekstra Tinggi 275 kV dan 500 kV, Badan Penerbit PLN, Jakarta, 2010.
[4]
Bonar Pandjaitan, Praktik-praktik Proteksi Sistem Tenaga Listrik, CV Andi Offset, Yogyakarta, 2013.
[5]
Cekmas Cekdin, Taufik Barlian, Transmisi Daya Listrik, Penerbit Andi, Yogyakarta, 2013.
[6]
Edy Supriyadi, Sistem Pengaman Tenaga Listrik, Perbit Adi Cita, Yogyakarta, 1999.
[7]
Fakhrul Rozy, Analisa Sistem Proteksi Relay Line Current Differential 500 kV pada GI Gandul, Jakarta, 2012.
[8]
Irvan Affandi, Analisa Setting Relai Arus Lebih dan Relai Gangguan Tanah Pada Penyulang Sadewa di GI Cawang, Depok, 2009.
[9]
J. Schlabbach, Short-Circuit Current, The Institution of Engineering and Technology, United Kingdom, 2005
[10]
J. Lewis Blackburn and Thomas J. Domin, Protective Relaying Principles and Applications 3rd Edition, USA : Taylor & Francis Group, 2006
[11]
Muhammad Taqiyyuddin Alawiy, Proteksi Sistem Tenaga Listrik, Malang, 2006.
50 http://digilib.mercubuana.ac.id/
51
[12]
Pengujian Relai Dasar,Badan Penerbit PLN, PT PLN (Persero) Pusat Pendidikan dan Pelatihan Udiklat Bogor, Jakarta, 2010.
[13]
Proteksi dan Kontrol Penghantar, Badan Penerbit PLN, Jakarta, 2010.
http://digilib.mercubuana.ac.id/
LAMPIRAN
52 http://digilib.mercubuana.ac.id/
53
FOTO INSTALASI RELE GE UR L90
http://digilib.mercubuana.ac.id/
GE Digital Energy
L90 Line Current Differential System UR Series Instruction Manual L90 revision: 6.0x Manual P/N: 1601-0081-X3 (GEK-113624A)
831776A2.CDR
Markham, Ontario
LISTED IND.CONT. EQ. 52TL
G
650 Markland Street
ISO 9001
E
IN
GE Digital Energy
S T ER GI
ED
RE
E83849
M U LT I L
GE Multilin's Quality Management System is registered to ISO 9001:2008
Canada L6C 0M1 Tel: +1 905 927 7070 Fax: +1 905 927 5098
QMI # 005094 UL # A3775
Internet: http://www.GEDigitalEnergy.com
*1601-0081-X3* http://digilib.mercubuana.ac.id/
2.1 INTRODUCTION
2 PRODUCT DESCRIPTION
Table 2–1: ANSI DEVICE NUMBERS AND FUNCTIONS DEVICE NUMBER
2
FUNCTION
DEVICE NUMBER
FUNCTION
49
Thermal overload protection
67P
Phase directional overcurrent
50BF
Breaker failure
67_2
Negative-sequence directional overcurrent
50DD
Adaptive fault detector (sensitive current disturbance detector)
68
Power swing blocking
78
Out-of-step tripping
50G
Ground instantaneous overcurrent
79
Automatic recloser
50N
Neutral instantaneous overcurrent
81O
Overfrequency
50P
Phase instantaneous overcurrent
81R
Rate of change of frequency
50_2
Negative-sequence instantaneous overcurrent
81U
Underfrequency
51G
Ground time overcurrent
87L
Segregated line current differential
51N
Neutral time overcurrent
87LG
Ground line current differential
0RQLWRULQJ
''
3
&ORVH
B
3
*
7ULS
B
%)
/
/*
3
3
1
1
14
'DWDIURPWRUHPRWHHQG YLDGHGLFDWHGFRPPXQLFDWLRQV
1
3
7UDQVGXFHULQSXWV 0HWHULQJ )OH[(OHPHQW70
*
3
*
1 ;
;
//LQH'LIIHUHQWLDO3URWHFWLRQ6\VWHP $8&'5
Figure 2–1: SINGLE LINE DIAGRAM
2-2
L90 Line Current Differential System http://digilib.mercubuana.ac.id/
GE Multilin
2 PRODUCT DESCRIPTION
2.1 INTRODUCTION
Table 2–2: OTHER DEVICE FUNCTIONS FUNCTION
FUNCTION
FUNCTION
Breaker Arcing Current (I2t)
Fault Locator
Open Pole Detector
Breaker Control
Fault Reporting
Oscillography
Breaker Flashover
FlexElements™ (8)
Pilot Scheme (POTT)
Broken Conductor Detection
FlexLogic™ Equations
Setting Groups (6)
Contact Inputs (up to 96)
IEC 61850 Communications (optional)
Stub Bus Synchrophasors
Contact Outputs (up to 64)
L90 Channel Tests
Control Pushbuttons
Line Pickup
Time Synchronization over SNTP
CT Failure Detector
Load Encroachment
Transducer Inputs/Outputs
Data Logger
Metering: Current, Voltage, Power, Energy, Frequency, Demand, Power Factor, 87L current, local and remote phasors
User Definable Displays User Programmable Pushbuttons
Direct Inputs (8 per L90 comms channel)
Modbus Communications
User Programmable Self-Tests
Disconnect Switches
Modbus User Map
Virtual Inputs (64)
Digital Counters (8) Digital Elements (48)
User Programmable LEDs
DNP 3.0 or IEC 60870-5-104 protocol
Non-Volatile Latches
Virtual Outputs (96)
Event Recorder
Non-Volatile Selector Switch
VT Fuse Failure
GE Multilin
L90 Line Current Differential System http://digilib.mercubuana.ac.id/
2
2-3
2.1 INTRODUCTION
2 PRODUCT DESCRIPTION 2.1.2 FEATURES
LINE CURRENT DIFFERENTIAL:
2
•
Phase segregated, high-speed digital current differential system.
•
Overhead and underground AC transmission lines, series compensated lines.
•
Two-terminal and three-terminal line applications.
•
Zero-sequence removal for application on lines with tapped transformers connected in a grounded wye on the line side.
•
GE phaselets approach based on the Discrete Fourier Transform with 64 samples per cycle and transmitting two timestamped phaselets per cycle.
•
Adaptive restraint approach improving sensitivity and accuracy of fault sensing.
•
Increased security for trip decision using disturbance detector and trip output logic.
•
Continuous clock synchronization via the distributed synchronization technique.
•
Increased transient stability through DC decaying offset removal.
•
Accommodates up to five times CT ratio differences.
•
Peer-to-peer (master-master) architecture changing to master-slave via DTT (if channel fails) at 64 kbps.
•
Charging current compensation.
•
Interfaces direct fiber, multiplexed RS422 and G.703 connections with relay ID check.
•
Per-phase line differential protection direct transfer trip plus eight user-assigned pilot signals via the communications channel.
•
Secure 32-bit CRC protection against communications errors.
•
Channel asymmetry (up to 10 ms) compensation using GPS satellite-controlled clock.
BACKUP PROTECTION: •
DTT provision for pilot schemes.
•
Three zones of distance protection with POTT scheme, power swing blocking and out-of-step tripping, line pickup, and load encroachment.
•
Two-element time overcurrent and two-element instantaneous overcurrent directional phase overcurrent protection.
•
Two-element time overcurrent and two-element instantaneous overcurrent directional zero-sequence protection.
•
Two-element time overcurrent and two-element instantaneous overcurrent negative-sequence overcurrent protection.
•
Undervoltage and overvoltage protection.
ADDITIONAL PROTECTION: •
Breaker failure protection.
•
Stub bus protection.
•
VT and CT supervision.
•
GE Multilin sources approach allowing grouping of different CTs and VTs from multiple input channels.
•
Open pole detection.
•
Breaker trip coil supervision and seal-in of trip command.
•
FlexLogic™ allowing creation of user-defined distributed protection and control logic.
CONTROL: •
One and two breaker configuration for breaker-and-a-half and ring bus schemes, pushbutton control from the relay.
•
Auto-reclosing and synchrochecking.
•
Breaker arcing current.
2-4
L90 Line Current Differential System http://digilib.mercubuana.ac.id/
GE Multilin
2 PRODUCT DESCRIPTION
2.1 INTRODUCTION
MONITORING: •
Oscillography of current, voltage, FlexLogic™ operands, and digital signals (1 × 128 cycles to 31 × 8 cycles configurable).
•
Events recorder: 1024 events.
•
Fault locator.
METERING: •
Actual 87L remote phasors, differential current, channel delay, and channel asymmetry at all line terminals of line current differential protection.
•
Line current, voltage, real power, reactive power, apparent power, power factor, and frequency.
COMMUNICATIONS: •
Front panel RS232 port: 19.2 kbps.
•
One or two rear RS485 ports: up to 115 kbps.
•
10Base-F Ethernet port supporting the IEC 61850 protocol. 2.1.3 ORDERING
a) OVERVIEW The L90 is available as a 19-inch rack horizontal mount or reduced-size (¾) vertical unit and consists of the following modules: power supply, CPU, CT/VT, digital input and output, transducer input and output, and inter-relay communications. Each of these modules can be supplied in a number of configurations specified at the time of ordering. The information required to completely specify the relay is provided in the following tables (see chapter 3 for full details of relay modules). Order codes are subject to change without notice. CPU modules 9G, 9H, 9L, and 9M are obsolete. See http://www.gedigitalenergy.com/multilin/order.htm for the latest ordering options. NOTE
The order code structure is dependent on the mounting option (horizontal or vertical) and the type of CT/VT modules (regular CT/VT modules or the HardFiber modules). The order code options are described in the following sub-sections.
GE Multilin
L90 Line Current Differential System http://digilib.mercubuana.ac.id/
2-5
2
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
PT PLN (PERSERO)
Doc. No.
P3BJB-TRS/04/05/2015/019
Cinere 16514 – Jakarta Selatan
Valid.
MEI 2015
PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI
DAFTAR SETELAN RELE PROTEKSI GI 150 KV INDOLIBERTY
1.
Proteksi : Penghantar 150 kV arah Konsumen
Jenis relai
:
Merek/Tipe relai LOKASI PROTEKSI L1, L2 L3, L4 Z1 Z11 Z21 Z0 CT Lokal CT Remote PT
: : : : : : : : : : : :
Line Current Differential Distance relay GE Multilin /L90 Indoliberty Konsumen 0.5 0.0777 0.0777 0.0777 0.2277 400 300 150
SCHEME POTT
:
DISABLED
L90 POWER SYSTEM 1 2 3 4 5 6
Number of Terminals Number of Channels Charging Current Compens. Pos Seq Cap React. (XC1) Zero Seq Cap React. (XC0) Zero Seq Current Rem.
2 1 Disabled 0.100 0.100 Disabled
, , +j +j +j +j / / KV /
0.5 0.2036 0.2036 0.2036 0.6108 1 1 100
km km Ω/km Ω/km Ω/km Ω/km Ampere Ampere Volt
7 8 9 10 11 12
Local Relay ID Terminal 1 ID Chan Asymmetry Comp Block GPS Time Ref Max Chan Asymmetry Round Trip Time Chang
1 2 OFF OFF 10.0 1.5
Enabled SRC 1 87L diff ch1 fail 0.2 pu 0.75 20 %
7 8 9 10 11 12
Restraint 2 Breakpoint DTT Key DTT Target Events
60 2.86 Enabled OFF Latched Enabled
1 (Enabled) 0 (SRC 1) 1-Pole 50DD SV OFF
6 7 8 9
Seal-In Seal-In Pickup Target Events
Disabled 0.2 pu Latched Enabled
kohms kohms
ms ms
CURRENT DIFFERENTIAL 1 2 3 4 5 6
Function Signal Source Block Pickup CT Tap 1 Restraint 1
%
pu
87L TRIP 1 2 3 4 5
Function Source Mode Supervision Force 3 Phase
PHASE DISTANCE PARAMETER Function Direction Shape Reach
1 2 3 4
: : : :
Hal.
Daftar Setelan Rele Proteksi
1/5
GI 150 KV Indoliberty
ZONE 1 Disabled Dibuat : DIN
ZONE 2 Enabled Forward Mho 0.042
ZONE 3 Disabled -
Diperiksa : TMY
Ω
Disetujui : SPK
Rev 00
RUANG LINGKUP SERTIFIKASI ISO 9001:2000 PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK http://digilib.mercubuana.ac.id/ SISTEM JAWA BALI DI PT PLN (PERSERO) P3B JAWA BALI
PT PLN (PERSERO)
Doc. No.
P3BJB-TRS/04/05/2015/019
Cinere 16514 – Jakarta Selatan
Valid.
MEI 2015
PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI
DAFTAR SETELAN RELE PROTEKSI GI 150 KV INDOLIBERTY 5 6 7 8 9 10
RCA Comp Limit Dir RCA Dir Comp Limit Supervision Delay
: : : : : :
-
85 90 45 60 1.2 0.4
-
: : : : : : : : : : : : : : : : : :
ZONE 1 Disabled -
ZONE 2 Enabled Forward Quad 2.991 0.443 0 0 0.042 69.555 90 45 60 18.168 69.112 18.168 69.112 0.2 0.4
ZONE 3 Disabled -
Deg Deg Deg Deg Pu Sec
GROUND DISTANCE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
PARAMETER Function Direction Shape Z0/Z1 Mag Z0/Z1 Angle Z0M Z1 Mag Z0M Z1 Angle Reach RCA Comp Limit Dir RCA Dir Comp Limit Quad Right Blinder Quad Right Blinder RCA Quad Left Blinder Quad Left Blinder RCA Supervision Delay
LINE PICK UP (SOTF) 1 2 3 4
Function Phase IOC Line Pickup UV Pickup Line End Open Pickup Delay
Enabled 2 0.7 0.2
5 6 7
Line End Open Reset Delay OV Pickup Delay AR Coord Bypass
0.2 0.2 Enabled
POWER SWING ELEMENT 1 3
Function INN
SYNCHROCHECK 1 1 2 3 4 5 6 7
Function Block V1 Source V2 Source Max Volt Diff Max Angel Diff Max Freq Diff
pu pu sec
8 9 10 11
AR Coord Pickup Delay AR Coord Reset Delay Terminal Open Block
sec sec
12 13
Target Events
Enabled 20.187
2 4
SYNCHROCHECK 2
Enable Off SRC1 SRC2 6V 15 0 0.17 Hz
Hal.
Daftar Setelan Rele Proteksi
2/5
GI 150 KV Indoliberty
FORBL Delay Pickup
1 2 3 4 5 6 7 Dibuat : DIN
Function Block V1 Source V2 Source Max Volt Diff Max Angel Diff Max Freq Diff
Diperiksa : TMY
Deg Deg Ω Deg Deg Deg Deg Ω Deg Ω Deg Pu Sec
0.045 sec 0.005 sec Status CB off SRC1 VT FUSE FAIL OP Latched Enabled
0.054 50 ms Enable Off SRC1 SRC2 6V 15 0 0.17 Hz Disetujui : SPK
Rev 00
RUANG LINGKUP SERTIFIKASI ISO 9001:2000 PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK http://digilib.mercubuana.ac.id/ SISTEM JAWA BALI DI PT PLN (PERSERO) P3B JAWA BALI
PT PLN (PERSERO)
Doc. No.
P3BJB-TRS/04/05/2015/019
Cinere 16514 – Jakarta Selatan
Valid.
MEI 2015
PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI
DAFTAR SETELAN RELE PROTEKSI GI 150 KV INDOLIBERTY 8 9 10 11 12 13 14
Dead Source Select Dead V1 Max Volt Dead V2 Max Volt Live V1 Min Volt Live V1 Min Volt Target Event
LOAD ENCROACHMENT 1 Function 2 Source 3 Min Volt 4 Reach 5 Angle
DV1 and LV2 0.2 pu 0.2 pu 0.9 pu 0.9 pu Self Reset Enable
8 9 10 11 12 13 14
Dead Source Select Dead V1 Max Volt Dead V2 Max Volt Live V1 Min Volt Live V1 Min Volt Target Event
DV2 and LV1 0.2 pu 0.2 pu 0.9 pu 0.9 pu Self Reset Enable
Enable SRC 1 0.250 20.187 30
6 7 8 9 10
Pickup Delay Reset Delay Block Target Events
0 0 OFF Disabled Enabled
AUTORECLOSER 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15 16 17
LINE 1 2 3
Function Mode Max Number Of Shots Block BKR1 Close Time BKR1 BKR Man Close Block Time Upon Manual Close 1 P Initiate 3 P Initiate 3 P TD Initiate Multi P Fault BKR 1 Pole Open BKR 3 Pole Open 3-P Dead Time 1 3-P Dead Time 2 Extend Dead T1 Dead T1 Exten
Enable 1 Pole 1 OFF 0.15 ON 10s
18 19 20 21 22 23 24
Reset Reset Time BKR Closed Block Pause Inc Seq Time Block BKR2
RESET OP 60 s CB CLOSE On AR Block On OFF 40 s OFF
AR INIT On OFF OFF OFF CB OPEN On OFF 1s 1.2 OFF 0.7 s
25 26 27 28 29 30 31 32 33 34
Close Time BKR2 Transfer 1 To 2 Breaker Closed
0.15 No No
BKR1 Fail Option BKR2 Fail Option 1-P Dead Time 1 BKR Sequence Transfer Time Event
Continue Continue 1s 1 4 Enable
Zero Seq (Z0) Angle Line Length Unit Line Length
69.55506 Km 0.5
Positive Seq (Z1) Mag Positive Seq (Z1) Angle Zero Seq (Z0) Mag
OSCILLOGRAPH
Number of Record Trigger mode Trigger position Trigger Source AC Input Waveform Digital Chanel 1 Digital Chanel 2 Digital Chanel 3 Digital Chanel 4 Digital Chanel 5
pu Ohm deg
0.108961 69.11161 0.325931
Ohm Deg Ohm
4 Automatic Overwrite 10 % START OSC On (VO16) 64 samples/cycle Start Z1 R On (VO23) Start Z1 S On (VO24) Start Z1 T On (VO25) Start Z2 R On (VO26) Start Z2 S On (VO27)
Hal.
Daftar Setelan Rele Proteksi
3/5
GI 150 KV Indoliberty
Dibuat : DIN
4 5 6
Digital Chanel 44 Digital Chanel 46 Digital Chanel 47 Digital Chanel 48 Digital Chanel 49 Digital Chanel 50 Digital Chanel 51 Digital Chanel 52 Digital Chanel 53 Digital Chanel 54 Diperiksa : TMY
Sec Sec
Deg Km
OPEN POLE OP PHASE SELECT AG PHASE SELECT BG PHASE SELECT CG PHASE SELECT AB PHASE SELECT BC PHASE SELECT CA PHASE SELECT SLG PHASE SELECT MULTI-P PHASE SELECT 3P Disetujui : SPK
Rev 00
RUANG LINGKUP SERTIFIKASI ISO 9001:2000 PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK http://digilib.mercubuana.ac.id/ SISTEM JAWA BALI DI PT PLN (PERSERO) P3B JAWA BALI
PT PLN (PERSERO)
Doc. No.
P3BJB-TRS/04/05/2015/019
Cinere 16514 – Jakarta Selatan
Valid.
MEI 2015
PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI
DAFTAR SETELAN RELE PROTEKSI GI 150 KV INDOLIBERTY Digital Chanel 6 Digital Chanel 7 Digital Chanel 8 Digital Chanel 9 Digital Chanel 10 Digital Chanel 11 Digital Chanel 12 Digital Chanel 13 Digital Chanel 14 Digital Chanel 15 Digital Chanel 19 Digital Chanel 20 Digital Chanel 21 Digital Chanel 23 Digital Chanel 24 Digital Chanel 25 Digital Chanel 26 Digital Chanel 27 Digital Chanel 28 Digital Chanel 29 Digital Chanel 30 Digital Chanel 32 Digital Chanel 33 Digital Chanel 34 Digital Chanel 35 Digital Chanel 36 Digital Chanel 37 Digital Chanel 38 Digital Chanel 39 Digital Chanel 40 Digital Chanel 41 Digital Chanel 42 Digital Chanel 43
Start Z2 T On (VO28) Start Z3 R On (VO34) Start Z3 S On (VO35) Start Z3 T On (VO36) Trip Zone1 (VO19) Trip Zone2 (VO20) Trip Zone3 (VO21) SEND DIST On (VO8) REC DIST On(W1a) PUTT OP PH SELECT ABG On (VO29) PH SELECT BCG On (VO30) PH SELECT CAG On (VO31) LINE PICKUP OP POWER SWING BLOCK POWER SWING UN/BLOCK BLOK AR On (VO7) Ext Blk Dist On (W2a) ExtAR Recl A On (W3a) ExtAR Recl B On (W4a) Ext Ledl RST On (W5a) TRIP PHASE A TRIP PHASE B TRIP PHASE C TRIP 1-POLE TRIP 3-POLE OFF OFF OFF OFF OFF OFF OFF
Digital Chanel 55 Digital Chanel 56 Digital Chanel 57 Digital Chanel 58 Digital Chanel 59 Digital Chanel 60 Digital Chanel 61 Digital Chanel 62 Digital Chanel 63 Analog Chanel 1 Analog Chanel 2 Analog Chanel 3 Analog Chanel 4 Analog Chanel 5 Analog Chanel 6 Analog Chanel 7 Analog Chanel 8 Analog Chanel 9 Analog Chanel 10 Analog Chanel 11 Analog Chanel 12 Analog Chanel 13 Analog Chanel 14 Analog Chanel 15 Analog Chanel 16
PHASE SELECT VOID POWER SWING 50DD POWER SWING OUTER POWER SWING INNER POWER SWING TRIP OFF OFF OFF OFF SRC1 I0_MAG SRC1 I0_ANGLE SRC1 I1_MAG SRC1 I1_ANGLE SRC1 I2_MAG SRC1 I2_ANGLE SRC1 V0_MAG SRC1 V0_ANGLE SRC1 V1_MAG SRC1 V1_ANGLE SRC1 V2_MAG SRC1 V2_ANGLE Tracking Frequency OFF OFF OFF
Proteksi Cadangan : Penghantar 150 kV arah Konsumen JENIS RELAI OCR dan GFR sisi 150 kV
TIPE RELAI
SETELAN YANG DIUSULKAN ( nilai sekunder )
EVALUASI PLN P3B ( nilai sekunder ) CT Ratio : 800/1 09 Configuration Setting Group 1 Overcurent Earth Fault 1 Earth Fault 2 CB Fail Setting Values
GE F35
Enabled Enabled Enabled Disabled Disabled Secondary
0A CT Ratios Hal.
Daftar Setelan Rele Proteksi
4/5
GI 150 KV Indoliberty
Dibuat : DIN
Diperiksa : TMY
Disetujui : SPK
Rev 00
RUANG LINGKUP SERTIFIKASI ISO 9001:2000 PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK http://digilib.mercubuana.ac.id/ SISTEM JAWA BALI DI PT PLN (PERSERO) P3B JAWA BALI
PT PLN (PERSERO)
Doc. No.
P3BJB-TRS/04/05/2015/019
Cinere 16514 – Jakarta Selatan
Valid.
MEI 2015
PENYALURAN DAN PUSAT PENGATUR BEBAN JAWA BALI
DAFTAR SETELAN RELE PROTEKSI GI 150 KV INDOLIBERTY Phase CT Primary Phase CT Sec’y E/F CT Primary E/F CT Secondary
400 A 1A 400 A 1A
Group 1 35 Group 1 Overcurrent 3501 I>1 Function 3502 I>1 Direction 3503 I>1 Current Set 3505 I>1 TMS 3508 I>1 tReset 3509 I>2 Function 3511 I>3 Status 3516 I>4 Status
IEC S Inverse Non-Directional 1.2 A (sec’y) 0.506 0s Disabled Disabled Disabled
38 Group 1 Earth Fault 1 3802 IN1>1 Function 3803 IN1>1 Direction 3804 IN1>1 Current Set 3806 IN1>1 TMS 3809 IN1>1 tReset 380A IN1>2 Function 3812 IN1>3 Status 3516 IN1>4 Status
JENIS RELAI Check synchronizing
TIPE RELAI
IEC S Inverse Non-Directional 0.2 A (sec’y) 0.77 0s Disabled Disabled Disabled
EVALUASI P3B ( nilai sekunder ) PT = 150 kV/100 V Vn = 57.7 V Using internal autoreclose
Check Synchronizing Settings Group A Power System Data 2 1103 Measure Full Scale Voltage100% Synchronism and Voltage Check 3501 25 Synchronism and Voltage Check 3502 Voltage threshold dead line / bus 3503 Voltage threshold live line / bus 3504 Maximum permissible voltage 3507 Maximum duration of synchronism-check 3510 Operating mode with MC 3511 Maximum voltage difference 3512 Maximum frequency difference 3513 Maximum angle difference
Hal.
Daftar Setelan Rele Proteksi
5/5
GI 150 KV Indoliberty
Dibuat : DIN
Diperiksa : TMY
150 kV ON 20 V 90 V 110 V 0.5 s Without CB closing time 10 V 0.17 Hz 0 15
Disetujui : SPK
Rev 00
RUANG LINGKUP SERTIFIKASI ISO 9001:2000 PENGEMBANGAN DAN PEMBINAAN INSTALASI PENYALURAN TENAGA LISTRIK http://digilib.mercubuana.ac.id/ SISTEM JAWA BALI DI PT PLN (PERSERO) P3B JAWA BALI
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/
http://digilib.mercubuana.ac.id/