FUNGSI DARI SWITCHGEAR : PERALATAN PEMUTUS DAYA YANG FUNGSI UTAMANYA MENCATAT DAN MEMUTUSKAN DAYA LISTRIK KE PERALATAN / BEBAN. SWITCHGEAR (CIRCUIT BREAKER) TEGANGAN RENDAH YANG DIBAHAS ADALAH JENIS A.C.B. TIPE DS 416 MERK MITSUBISHI
Tr -
RATING DARI BREAKER TIPE DS 416 :
TIPE
TEGANGAN ( VOLT )
FRAME SIZE ( A )
600
RATED/ INTERUPTING CURRENT ( KA-SYM ) 42
DS 416 500 250
11212/HI/TR/KJ/MYN/min
Doc 12/1.1.12/1/97
1600
50 50
Tr - 2
11212/HI/TR/KJ/MYN/min
Doc 12/1.1.12/1/97
Tr - 3
PROSEDUR PELEPASAN SWITCHGEAR LANGKAH-LANGKAH : - KOMUNIKASI HARUS JELAS - KEPERLUAN HARUS JELAS - KEDUDUKAN / POSISI BREAKER SETELAH DILEPAS. - SISTEM PENGAMANAN DIPERLUKAN ATAU TIDAK UNTUK PELEPASAN DILAKUKAN DENGAN 3 CARA PENGOPERASIAN : - OPERASI SECARA REMOTE - OPERASI SECARA LOKAL - OPERASI MANUAL
PROSEDUR PELEPASAN SWITCHGEAR SECARA REMOTE - YAKINKAN SELECTOR SWITCH PENGOPERASIAN PADA POSISI REMOTE - PASTIKAN SWITCHGEAR (CIRCUIT BREAKER) AKAN DILEPAS. - LEPAS CIRCUIT BREAKER DENGAN MENGGUNAKAN SAKLAR START / STOP DENGAN MENGGERAKKAN BERLAWANAN ARAH JARUM JAM ATAU PUSH BUTTON ON/OFF. - PASTIKAN KONTAK BREAKER SUDAH TERBUKA “OPEN” DENGAN MEMPERHATIKAN INDIKASI CONTACT POSITION. BENDERA - HIJAU LAMPU - HIJAU NYALA DAN MERAH HATI. - LAKSANAKAN LANGKAH-LANGKAH KERJA SELANJUTNYA SESUAI DENGAN PETUNJUK.
PELEPASAN SECARA OPERASI LOKAL - SELECTOR SWITCH PENGOPERASIAN POSISI “LOCAL”. - PELEPASAN DILAKUKAN DENGAN MENGGERAKKAN TRIP PLAT. - PERHATIKAN CONTACT POSITION INDICATOR BENDERA HIJAU ATAU NOL (0) BAHWA KONTAK TERBUKA “OPEN”.
PELEPASAN SECARA MANUAL - DILAKUKAN DILUAR CUBICLE. - CHARGING PEGAS PEMASUKKAN. - MASUKKAN BREAKER DENGAN MENEKAN TOMBOL PEMASUKKAN (CLOSE BUTTON) - LEPAS CIRCUIT BREAKER DENGAN MENEKAN TRIP PLAT DAN PERHATIKAN KONTAK SECARA PENGAMATAN SUDAH TERBUKA “OPEN”. 11212/HI/TR/KJ/MYN/min
Doc 12/1.1.12/1/97
Tr - 6
PROSEDUR PELEPASAN SWITCHGEAR
TERDAPAT 3 KEDUDUKAN / POSISI BREAKER DI CUBICLE : 1. 2. 3. 4.
POSISI CONNECTED POSISI TEST POSISI DISCONNECTED DRAW OUT ( DILUAR CUBICLE ).
- POSISI CONNECTED
: PRIMARY JUNCTION TERHUBUNG, SECONDARY JUNCTION TERHUBUNG - POSISI TEST : PRIMARY JUNCTION TIDAK TERHUBUNG, SECONDARY JUNCTION TERHUBUNG - POSISI DISCONNECTED : PRIMARY & SECONDARY JUNCTION TIDAK TERHUBUNG, - DRAW OUT : BREAKER DILUAR CUBICLE ( PRIMARY DAN SECONDARY JUNCTION TIDAK TERHUBUNG )
11212/HI/TR/KJ/MYN/min
Doc 12/1.1.12/1/97
Tr - 7
PEMERIKSAAN KOMPONEN UTAMA PEMERIKSAAN ARC CHUTE : TANDA-TANDA TERBAKAR, DEPOSITE, KERETAKAN INSULATING PLATE A DAN
INSULATING PLATE B, KEDALAMAN ALUR, PERMUKAAN MOULDED CASE, KERETAKAN.
11212/HI/TR/KJ/MYN/min
Doc 12/1.1.12/1/97
Tr - 8
KONTAK UTAMA DAN KONTAK BANTU - PERMUKAAN KONTAK : KASAR / TIDAK RATA, KETEBALAN LAPISAN ( + 1mm ) JARAK PERMUKAAN KONTAK UTAMA SAAT KONTAK BUSUR MASUK TIDAK KURANG DARI 3 mm, KELURUSAN SAAT MASUK, JARAK KERUSAKAN BUSUR SAAT BREAKER CLOSE TIDAK BOLEH KURANG DARI 1 mm.
11212/HI/TR/KJ/MYN/min
Doc 12/1.1.12/1/97
Tr - 9
KOMPONEN MEKANIS PENGGERAK - PERIKSA SECARA VISUAL TERHADAP KOTORAN, DEBU DAN BENDA-BENDA. - PERIKSA TEST SISTEM KERJA MEKANIS. - PERIKSA PELUMASAN BEARING - TEST PUTARAN DARI PENGUJIAN TRIP ( TRIP LATH ) NO.4
CLOSING DAN TRIPPING COIL - PERIKSA SECARA VISUAL : ISOLASI DAN KUMPARAN KOIL. - UKUR TAHANAN ISOLASI DENGAN MENGGUNAKAN MEGGER 500 VOLT
INTERLOCK MEKANIS FUNGSI INTERLOCK : MENGHINDARI TERJADINYA KESALAHAN OPERASI YANG DAPAT MENGAKIBATKAN KERUSAKAN PERALATAN DAN BAHAYA / KESALAHAN TERHADAP MANUSIA FUNGSI CLOSING SPRING DISCHARGE INTERLOCK : MENCEGAH MASUKNYA BREAKER PADA SAAT POSISI DISCONNECTED PEMERIKSAAN YANG DILAKUKAN : SISTEM KERJANYA
INTERLOCK MEKANIS - PERIKSA SISTEM KERJA SHUTTER FUNGSI INTERLOCK INI ADALAH UTNUK MENCEGAH AGAR BREAKER PADA POSISI CLOSE, BREAKER TIDAK DAPAT DIKELUARKAN ATAU DIGERAKKAN DARI BILIKNYA ( CUBICLE ), SALAH COBA MERUSAK KONTAK ISOLASI PRIMARY JUNCTION DAN MEMBAHAYAKAN PETUGAS
PAD LOCKING PEMERIKSAAN : SISTEM KERJANYA FUNGSINYA : - MENGUNCI BREAKER TIDAK DAPAT DIMASUKKAN ATAU DIKELUARKAN - MENGUNCI BREAKER AGAR TIDAK CEPAT DIMASUKKAN, WALAUPUN DAPAT DIKELUARKAN.
SOLID STATE REGULATOR - PERIKSA KELONGGARAN SKRUP-SKRUP. - PERIKSA DIAL DENGAN EKIVALEN ARUS TRAFO SISI SEKUNDER
TRIP AKTUATOR
PEMERIKSAAN TRAFO TEGANGAN : - UKUR DAN CATAT TEGANGAN TRAFO : PRIMER DAN SEKUNDER . - CHECK ISOLASI, BELITAN, BODI SECARA VISUAL - UKUR TAHANAN ISOLASI
TRAFO ARUS : KERETAKAN DAN UKUR ARUS TRAFO DAN TAHANAN ISOLASINYA
PEMBERSIHAN SWITCHGEAR -BERSIHKAN CUBICLE DENGAN UDARA BERSIH DAN KERING.
-ARC SHUTE, KONTAK-KONTAK MEKANIS : UDARA BERSIH. -KONTAK BUSUR, KONTAK UTAMA, KONTAK BANTU DAN OLESKAN DENGAN GRAPHITE GREASE SECUKUPNYA. -KOMPONEN MEKANIK : BERSIHKAN KOTORAN, DEBU DAN BENDA-BENDA ASING, GUNAKAN KUAS, LEMARI BAGIAN-BAGIAN YANG BERGERAK -MOULDED BAGIAN BAWAH BERSIHKAN TERHADAP DEOPSITE
PENGETESAN OPERASI SWITCHGEAR SECARA MANUAL : DILUAR CUBICLE. SECARA ELCTRICAL : DIDALAM CUBICLE / POSISI TEST. SECARA MANUAL : - ISI PEGAS SECARA MANUAL, PERHATIKAN INDIKATOR SPRING CHARGE. - TEKAN TOMBOL PEMASUKKAN, PERHATIKAN SECARA VISUAL BREAKER CONTACT POSITION INDIKATOR ATAU PERHATIKAN KEDUDUKAN KONTAK UTAMA - LEPAS BREAKER DENGAN MENEKAN TRIP PLATE.
SECARA ELEKTRICAL : - MASUKKAN BREAKER KE CUBICLE - POSISIKAN KEDUDUKAN BREAKER PADA POSISI TEST. - MASUKKAN POWER SUPLAI UNTUK KONTROL : PEGAS AKAN TERISI BILA DI LENGKAPI DENGAN CHARGING OTOMATIS ATAU ISI PEGAS SECARA MANUAL - MASUKKAN KONTAK BREAKER DENGAN MENEKAN PUSH BUTTON “CLOSE” DAN LEPAS KONTAK BREAKER DENGAN TRIP PLATE.
KONDISI-KONDISI YANG HARUS TERPENUHI SAAT MEMASUK KAN BREAKER PADA LOKAL OPERASI MAUPUN REMOTE OPERASI - BREAKER DAPAT DIMASUKKAN PADA POSISI TEST DAN CONNECTED. - LEVERING HANDLE DILEPAS DARI BREAKER, SHUTTER HARUS NAIK DAN TRIP PLATE HARUS RESET. - CLOSING SPRING DAPAT DIISI.